2nd System Option Code Page 18
Default
Zone Light ON
Zone Light 1
Zone 4 N.O. without EOL
Zone Light 2
Master Code not changeable
Zone Light 3
Siren Squawk enabled.
Zone Light 4
NOT USED
“Ready” Light
6th code is maid’s code
“Armed” Light
1400 Hz Radionics
Zone Light OFF
Zone
4
normal
Master Code changeable
Siren Squawk disabled
NOT USED
6th code normal
2300 Hz Radionics
l
With Siren Squawk enabled, the siren will sound one short burst on arming and two short
bursts on disarming.
3rd
System Option Code Page 19
Default
Zone Light ON
Zone Light 1
Access Code req’d for bypass
Zone Light 2
Enabled
Zone Light 3
Periodic downloading
Zone Light 4
access code required
“Ready” Light
audible (buzzer)
“Armed” Light
Partial closing identified
Communication
Variables Page 79
Default
Maximum transmissions per burglary zone
Zone Light OFF
Code not required
Disabled
Periodic test transmit
no code required
silent
Not identified
Enter digits from
to “99” for number of transmissions per zone during the period as defined in Section
1st System Option Code, Zone Light 2; [00] unlimited transmissions per burglary zone. Note that
the Fire zone always transmits.
Zone
Bypass Mask Page
If the Zone Light is ON, the zone can be bypassed using the
command.
Default
Zone Light 1 If a zone is defined as a fire zone, it cannot be bypassed.
Zone Light 2
Zone Light 3
Zone Light 4
30
firealarmresources.com