3rd System Option Code
Refer to Section
for programming information.
LIGHT
ON =
Access code required for bypass
l
OFF =
Access code not required for bypass
ON =
Enable
downloading call feature
l
OFF
Disable
call feature’
ON =
Periodic
l
OFF =
Periodic test transmission
ON =
requires a Access Code
l
OFF
does not require Access Code
l
ON
Panic Alarm has keypad-audible feedback
OFF =
Panic Alarm does not have keypad-audible feedback
ON
Partial closings identified
3
. OFF =
Partial closings not identified
[R] = “Ready” light; [A] = “Armed” light
l
Factory default settings
allows downloading to be initiated from the control panel
The panel can be programmed to periodically call the downloading computer. The cycle time in days for
the call is set in Section
The automatic call to the downloading computer can be used to update the
panel program and/or to upload status information from the panel.
If partial closings to be identified, alarm codes for bypassed zones will be transmitted.
Communication Variables
Enter a
number in this Section. This number defines the number of attempts the communicator will make
to transmit alarm and
for
a zone before the communicator shuts down for that zone. The number
of attempts is for the period defined in Section
1st System Option Code, Light 2. The number of
communication attempts may be programmed from [00] to
where ‘00’ means the communicator will never
shut down. Note that the fire zone cannot be shut down; it always transmits.
Zone Bypass Mask
Refer to Section
for programming information. If a zone light is ON, that zone can be bypassed; if a zone light
is OFF, that zone cannot be bypassed using the
command. Note that the fire zone cannot be bypassed.
System
limes
Six system times are programmed in Section
each time requires a 2-digit number. Do not press the
Key during data entry.
Entry Delay
(01 to 99 seconds) Location [I] holds the standard Entry Delay time. The default setting is
30 seconds; refer to Section for information on Zone Definitions.
Exit Delay
(01 to 99 seconds) Location
holds the standard Exit Delay time. The default setting is 45
seconds; refer to Section for information on Zone Definitions.
Siren Cut-Off
(01 to 99 minutes) Location
determines how long the siren will sound when an alarm is
generated. The default setting is 4 minutes.
AC Failure Transmission Delay (01
to 99 minutes) Location
determines the length of time before the
communicator will transmit an AC failure report. The default setting is 30 minutes.
1 9
firealarmresources.com