Advanced Programming
46
[901] Installer Walk Test Enable/Dis-
able
[*]
Function
When this mode is ON, all zones become 24-Hr non force-armable
zones that will sound the bell (steady or pulsed ) for 2 seconds and
transmit their programmed alarm reporting codes (
section [320-
323]
) when violated. If the user attempts to arm while in Walk Test
the keypad will sound an error.
☞
Fire Troubles are not supported in Walk Test.
Alarm Memory is cleared upon entering Walk Test.
To Enable Walk Test Mode:
Disable ‘Keypad Blanking’ - section [016] option 3
Disable ‘Fire Bell is Continuous’ - section[016] option 8
Enter from normal state:
[*] [8] [Install Code] [2] [901]
To Disable Walk Test Mode:
Re-enter:
[*] [8] [Install Code] [2] [901]
Re-enable ‘Keypad Blanking’ and ‘Fire Bell Continuous’ if
required.
☞
The User Walk Test (
[*][6][8]
) performs the same functions
as indicated here except that reporting codes are not trans-
mitted to the central station.
[902] Reset Module Supervision
All modules will automatically enroll within one minute upon
power-up. If modules are removed, enter this section to clear
any supervisory troubles that may be present. When this
mode is entered the system will attempt to re-enroll all
modules.
☞
When this section is entered, all pending Supervisory Trouble
Restorals will not be logged or transmitted.
☞
If a module is NOT communicating properly with the system,
it will be deleted when you enter this section.
To Reset Module Supervision:
Enter from normal state:
[*] [8] [Install Code] [2] [902]
[903] Module Supervision Field
When this section is entered, the system will display all mod-
ules enrolled on the system.
[*] [8] [Install Code] [2] [903]
[904] Device Placement Test
FLASH
Device Selection -
When this section is entered, a two digit entry is
required to select the zone number to be tested (01-32). If a device
is selected that is not enrolled, an error tone will sound.
Placement Indication -
After the zone is selected the device sends
a signal to the NT9005 to register a signal strength value. These
results are indicated in the following table.
Indication
LCD
Bell/Buzzer
Good
Bad
Not Enrolled
Good
Bad
-
1 Beep/Squawk
3 Beep/Squawk
Error Tone
RF Jam Detection -
For proper RF Jam detction, zones must be
placement tested in the location that they will be used. A zone must
register 3 ‘Good’ results in sequence for a successful test. After a
successful test the siren will sound for 2 seconds to indicate a suc-
cessful placement.
To Perform Module Placement Test
Enter from normal state:
[*] [8] [Install Code] [2] [904] [Zone]
Press
[#]
to cancel test.
[990] Installer Lockout Enable
When enabled, the panel will sound an audible indication on power-
up (the phone relay will click 10 times). This feature will have no
effect on a software default (all programming will return to the fac-
tory defaults). If a hardware default is attempted while lockout is
enabled, the default will not occur and the attempt will be logged to
the event buffer.
To Enable Installer Lockout -
Enter from normal state:
[*] [8] [Install Code] [2] [990] [Install Code] [990]
[991] Installer Lockout Disable
Disables the feature described above.
To Disable Installer Lockout -
Enter from normal state:
[*] [8] [Install Code] [2] [991] [Install Code] [991]
[996] Restore Wireless Default Programming
When enabled, all programming in the
RF section
[804]
will be
restored to factory defaults.
To Restore RF Factory Defaults -
Enter from normal state:
[*] [8] [Install Code] [2] [996] [Install Code] [996]
[999] Restore Factory Default Programming
Hardware Restore:
Factory default programming can be restored
by shorting terminals YI and G2 for 10 seconds during Power-up if
Installer Lockout (Sections [990],[991] is disabled.
Software Restore:
When enabled, all programming in the NT9005
will be restored to factory defaults.
☞
When this section is entered, the Module Supervision Field
will be reset. See
section [903]
.
To Restore Factory Defaults -
Enter from normal state:
[*] [8] [Install Code] [999] [Install Code] [999]