Chapter 2: Installation
2-1 Installation Procedure
Read the following procedure to familiarize yourself
with the necessary steps before installing the system.
1.
Create a Layout
- Draw a rough sketch of the
building and include all alarm detection devices,
modules and PGM output devices. Refer to the
following paragraphs for wiring requirements.
Keybus,Para 2-3.1
PGMs Para 2-3.2
Hardwired ZonesPara 2-3.3
Telephone Line Wiring.Para 2-3.4
Battery and AC Wiring. Para 2-3.5
Refer to paragraph 2-4 and the associated instal-
lation sheets for placement of wireless detectors.
Locate the control panel in a dry area, near an
unswitched AC source and telephone line. Avoid
areas that are a possible source of electrical noise
such as computers, televisions, appliances, HVAC
systems. Avoid areas with large metal surfaces
such as heating ducts.
☞
Ensure that the control panel and other
modules will be installed in an area that
will be protected by the system.
2.
Mount NT9204 Module -
Mount NT9204 mod-
ule as indicated in the associated installation
manual. Mount hardwired and PGM output
devices as required.
3.
Route Wiring -
Route the telephone line, AC
power line, PGM wiring, hardwired zone wiring
or Keybus wiring to the NT9005 panel location.
4.
Install NT9005 Back Cover
- Route wiring
through the access holes provided and mount the
back cover. Refer to paragraph 2.2 ‘NT9005
Installation’.
5.
Complete Wiring
- Connect the telephone line,
AC power line, PGM wiring, hardwired zone wir-
ing or Keybus wiring to the back cover.
6.
Power up Control Panel
- Connect the backup
battery. Place the unit on mounting plate ensur-
ing that the header on the printed circuit board
aligns with the terminal block on the back plate.
☞
The system will NOT power up if only the
battery is connected.
Ensure that the LCD display and buzzer are func-
tioning as described during the power up
sequence.
See Start-up, paragragh 1-5.1.
7.
Position and Enroll Wireless Detectors
. This
can be performed in Flash Programming or sec-
tion [904] in Advanced Programming (placement
only). Refer to the Installation Sheets of wireless
devices to determine optimal placement. Mount
wireless devices after succesful placement. Refer
to appendices C, D and E.
8.
Program the System
. The system can be quickly
programmed for basic setup in Flash Program-
ming or custom programmed manually in
Advanced Programming or with DLS2002 (down-
loading software) using a remote or local com-
puter.
See Chap. 3:Programming
.
9.
Test the System.
Two system tests are available:
the user Walk Test available in [*][6][8] program-
ming or the installer Walk Test described in sec-
tion [901] in Advanced Programming.
☞
In the User Walk Test report codes are not
sent to the central station.