Advanced Programming
22
[000][6] Keypad Programming
1
ON Local Clock Display Enabled
✓
System time will be displayed on the keypad
☞
The time is not displayed during
[*]
programming.
OFF Local Clock Display Disabled
2
ON Local Clock Displays AM/PM
OFF Local Clock Displays 24 Hour Time
✓
☞
Option 1 must be enabled (ON) for these option
s.
3
ON Open Zones Override Clock Display
If a zone goes ‘Open’ on the system the keypad will start
scrolling the open zone(s) without the user pressing a
key.
OFF Open Zones Do Not Override Display
✓
Open zones will not scroll until a key is pressed.
4
Future Use
5
ON Alarms NOT Displayed While Armed
When the system is armed there will be no indication of
zones being in alarm. The
Alarm
icon will not turn on
and the zones in alarm will not scroll.
OFF Alarms Displayed While Armed
✓
When the system is armed there will be a visual indication
of zones in alarm. The
Alarm
icon will turn on and the
zones in alarm will scroll.
6
ON Door Chime Enabled for Zone Openings
✓
If door chime is enabled and a chime zone goes open the
chime will sound.
OFF Door Chime Disabled for Zone Openings
If door chime is enabled and a chime zone goes open the
chime will NOT sound.
☞
Door chime is enabled/disabled with
[*][4]
7
ON Door Chime Enabled for Zone Closings
✓
If door chime is enabled and a chime zone is restored the
chime will sound.
OFF Door Chime Disabled for Door Closings
If door chime is enabled and a chime zone is restored the
chime will NOT sound.
☞
Door chime is enabled/disabled with
[*][4]
8
Future Use
[000][7] Keypad Priority Key Options
1
ON [F] Key Enable
✓
Holding the
[F]
Key is two seconds generates a fire alarm.
OFF [F] Key Disable
2
ON [A] Key Enable
✓
If the
[A]
Key is held for two seconds an auxiliary alarm is
generated.
OFF [A] Key Disable
3
ON [P] Key Enable
✓
If the
[P]
Key is held for two seconds a panic alarm is
generated.
OFF [P] Key Disable
4
ON Leading ‘0’ on Clock Displayed
OFF Leading ‘0’ on Clock Not Displayed
✓
5-8
Future Use
[001]-[004] Zone Definition
Op
Description
00
Null -
This zone will not operate in any way. For zones
not used and not requiring a closed loop or EOL resis-
tor. Typically used for zones that are not used.
01
Delay 1 -
If this zone is violated when the system is
armed, it will provide an entry delay. The keypad
buzzer will sound to warn the user that the system
must be disarmed. If the system is not disarmed
before the entry delay expires, an alarm will be gener-
ated. Typically this type of zone will be used for the
front door or any other entry/exit point. Refer to
sec-
tion [005] , ‘System Times’
, to program this delay.
02
Delay 2 -
This zone operates the same as Delay 1 but
provides a different entry delay. Typically this zone will
be used for a garage door. Refer to
section [005] ,
‘System Times’
, to program this entry delay.
03
Instant -
If this zone is violated when armed, it will
cause an instant alarm. Typically this zone is used for
windows and other perimeter type zones.
04
Interior -
If this type of zone is violated when the sys-
tem is armed it will follow entry delay if a delay type
zone was violated first. Otherwise it will cause an
instant alarm. Typically this zone type is used for inte-
rior protection devices such as motion detectors.