[371] Test Transmission Time of Day
39
[4] Transmission Delay
This value defines the delay before transmission. The delay is for
zones which have the Transmission Delay attribute enabled.
Default
000
I___I___I___I
000-255 Seconds
[5] AC Failure Communication Delay
This value determines the delay before an AC FAILURE or AC
RESTORE is reported. The AC failure or restoral is still displayed
immediately.
Default
030
I___I___I___I
000-255 Minutes
[6] TLM Trouble Delay
The number of valid checks (10 second interval) required before a
Telephone Line trouble is generated is programmed here. Valid
entries are 000-255 for trouble annunciation and transmission
(LINKS) delays of 10 to 2550 Seconds (42.5 Minutes).
Default
003
I___I___I___I
000-255 transmissions
000 = disabled
[7] Test Transmission Cycle (Land Line)
This value determines the period between Test Transmissions for the
land line. Valid entries are
[000]-[255]
. Whether this interval is in
minutes or days is determined in
section [702], option 3
.
Default
030
I___I___I___I
000-255 Days
[8] Not Used
[9] Zone Low Battery Transmission Delay
When a zone reports a low battery condition, it will be indicated
immediately on the keypad, but the transmission to the monitoring
station will be delayed by the value programmed in this section. If
the user does not correct the low battery condition before the delay
expires, the low battery condition will be transmitted. The low bat-
tery alarm and restoral codes will only be reported once per armed
period. The Low Battery Restore transmission is not delayed.
Default
007
I___I___I___I
000-255 Days
[10] Delinquency Transmission Delay
This value determines the time period that the Delinquency Event
will be postponed until it is logged to the event buffer and transmit-
ted. Whether this value is in hours or days is determined if Delin-
quency is for Activity (hours) or Closing (days) as specified in
section
[380] option 8
.
Default
030
I___I___I___I
000-255 Hours/Days
[371] Test Transmission Time of Day
Enter a 4-digit time using the 24 hour clock format (HH:MM). To
disable the test transmission, enter
[9999]
in this section.
Default 9999
I___I___I : I___I___I
00:00 - 23:59
99:99 to Disable
[380] First Communicator Option Codes
1
ON
Communications Enabled
✓
The system’s communicator will be enabled and all events
with reporting codes will be reported to the monitoring sta-
tion. Refer to the Telephone Number, Reporting Code and
Call Direction Programming sections.
OFF Communications Disabled
The system’s communicator will be shut off and events will
not be transmitted to the monitoring station. Downloading
may still be performed if enabled.
2
ON
Restorals on Bell Time-out
Zone restoral reporting codes will not be transmitted until the
zone has been restored
and
the bell cut-off time has expired.
If the zone is not restored when the bell cut-off time expires,
the restoral will be transmitted when the zone physically
restores or when the system is disarmed.
☞
24 Hour zones will not restore until the zone is physically
restored.
OFF Restorals follow Zones
✓
Zone restoral reporting codes will be transmitted when the
zone is physically restored. If the zones are still active when
the system is disarmed, the restoral codes will be transmitted
when the system is disarmed.
☞
24 Hour zones will not restore until the zone is physically
restored.
3
ON
Pulse Dialing
The control panel will dial telephone numbers using pulse
(rotary) dialing.
OFF DTMF Dialing
✓
The control panel will dial telephone numbers using DTMF
(dual tone multi-frequency) dialing.
4
ON
Switch to Pulse Dialing on Fifth Attempt
✓
If DTMF dialing is enabled (option [3]), the control panel will
dial telephone numbers using DTMF dialing for the first 4
attempts. If unsuccessful, the control panel will switch to
pulse (rotary) dialing for the remaining attempts.
OFF DTMF Dialing on All Attempts
If DTMF dialing is enabled, the control panel will dial tele-
phone numbers using DTMF dialing for all dialing attempts.
5
ON
Third Telephone No. Enabled
The 3rd phone number will be used for alternate dialing with
the 1st phone number or as a backup of the 1st phone num-
ber. See option 6
OFF Third Telephone No. Disabled
✓
The 3rd phone number will not be used.
firealarmresources.com
Содержание Envoy NT9005EU
Страница 58: ...NOTES firealarmresources com ...