Page: 50
d)
The system will determine what and how much of a correction to apply.
e)
A few calibrations will be required if there is a significant error.
3)
The advanced method determines how and what to adjust. This method also stores entries to
the micro SD Flash card if that option has been included.
4)
With either calibration methods it is possible to adjust the moisture offset for the product in
use at any time. The offset is a direct relationship to moisture. Increasing the existing offset by
adding 1.0 will increase the displayed value by 1.0. Decreasing the existing offset by subtracting
1.0 will decrease the displayed value by 1.0. It is possible to have negative numbers for the
offset.
5.11.10 Engineering Functions 8
–
Calibration Factor
Press “
Calibration Factor
”
“
Touch area
” to display the value entry
numeric keypad screen. Enter the desired value on the “Touch”
keypad.
Press the “
Touch area
”
<Exit>
to cancel and return to the main
screen
Press the “
Touch area
”
<Back>
to cancel and return to the
previous screen
Press the “
Touch area
”
<More>
to move to the next screen.
Figure 76.
–
Engineering Functions 8
–
Calibration Factor screen
How the Calibration Factor works:
The Calibration Factor is the amount of change applied with each calibration entry while using the
“Advanced” method.
The Logic limits the maximum difference between the online reading and the manual sample to 1%.
The calibration factor limits the change to the offset to a percentage of the difference. A calibration
factor of 0.5 means the offset will change by 50% of the difference and a calibration factor of 0.75 limits
the offset change to 75% of the difference, etc.
5.11.11 Engineering Functions 9
–
Moisture Output scaling
Press “
Maximum or Minimum
”
“
Touch area
” to display the value
entry numeric keypad screen. Enter the desired value on the
“Touch” keypad.
Press the “
Touch area
”
<Exit>
to cancel and return to the main
screen
Press the “
Touch area
”
<Back>
to cancel and return to the
previous screen
Press the “
Touch area
”
<More>
to move to the next screen.
Figure 77.
–
Engineering Functions 9
–
Moisture Output Scaling
SYSTEM
F1
F2
F3
F4
Exit
More
Calibration Factor
(0 to 1)
0.50
Back
SYSTEM
F1
F2
F3
F4
Exit
More
Moisture Output Scaling
Maximum
50.0%
Minimum
0.0%
Back
Содержание AM3
Страница 1: ......
Страница 84: ...Dryer Master AM3 Product Manual Dryer Master Inc Page 82 11 Appendix C IMO Set up Guide ...
Страница 85: ...Dryer Master AM3 Product Manual Dryer Master Inc Page 83 ...
Страница 86: ...Dryer Master AM3 Product Manual Dryer Master Inc Page 84 ...
Страница 87: ...Dryer Master AM3 Product Manual Dryer Master Inc Page 85 ...
Страница 88: ...Dryer Master AM3 Product Manual Dryer Master Inc Page 86 ...