ES-699 Rev F
Page 5 of 10
5.4
Description of SVI2-1 Marking
Masoneilan/DRESSER
AVON MA USA
0518
MODEL: SVI2-1bcdefg4
SN
–
nnywwnnnn
30 Volts, 4-20 mA, 80 PSI
Operating Temp
–
40 to +85
º
C
Type 4X
–
IP 66
T6 Ta=60
º
C, T5 Ta=75
º
C T4 Ta=85
º
C
ZELM 05ATEX0280X
Supply Connection Wiring Rated for 5
º
C Above Ambient
Intrinsically Safe Installed per ES-699
II 3 G
EEx nL IIC T6
Name and
address of
manufacturer
Certificate Number
Requirement to use high
temperature rated wiring.
Voltage, current and
pressure operating limits.
Operating
temp
limits
Serial
number
Surface
temperature
ignition codes
for gas
ATEX Logo
Number of Certified Body
Enclosure
Type
Model Designation
Requirement to
follow certified
installation
drawing
Bar
Code
II 2 G
EEx ia IIC T6
Maximum Surface Temperature
for Dust at Ta=85
°
C
EU Community
Compliance Mark
Category, types of
protection and gas
group designations
II 2 D, II 3 D T96
°
C
Specifications and References
Hazardous Location Installation