Check Out, Configuration and Calibration
Calibration
29
Auto Tune
To auto tune the SVI II AP:
1.
Press * to begin the autoTUNE procedure. This takes 3 to
10 minutes and strokes the valve in large and small steps
to set the PID parameters for best positioning response.
2.
When autoTUNE proceeds, numerical messages display,
indicating the procedure is working.
3.
When autoTUNE is complete, it will display TUNE.
4.
Press + repeatedly until
↑
SETUP appears.
5.
Press * to return to SETUP menu
↓
CALIB appears.