Masoneilan Dresser
SVI II AP Quick Start Guide
24
To power up the SVI II AP:
1.
Loosen the four (4) cover screws and remove the cover of
the SVI II AP. Connect the +
⁄
- terminals to the current
to + and - to -. See Figure 11 on page 21.
Reinstall the cover and display.
2.
Adjust current to 12 mA. Upon initial power up, of a newly
installed SVI II AP, the positioner will run in NORMAL
mode using the default instrument parameters installed at
the factory. The positioner will cycle through the NORMAL
cycle menu and LCD will display the following values:
PRES: Pressure - unit of measurement and value
SIGNAL
POS (Position)
3.
The LCD will also display an exclamation point (
!
) in the
top left corner of the display window. “
!”
indicates that
there is further instrument status available.
4.
Proceed to Configuration and Calibration.
Note:
If the SVI II AP is specified without local pushbuttons and
display, local operation is not available. Configure and calibrate
with ValVue 2.4 and a HART modem.
Configuration
Use the procedures that follow to: calibrate, tune, view configuration
data and status messages for the SVI II AP. Observe all warnings as
the valve moves during these procedures.
These procedures can cause the valve to move. Before proceeding be
sure the valve is isolated from the process. Keep hands clear from
moving parts.
Note:
All calibration and configuration procedures are described using
an SVI II AP with pushbuttons and display and ValVue 2.4
software.
ValVue 2.4 Software
The SVI II AP is shipped with a free version of ValVue 2.4 Lite and a trial
version of ValVue 2.4.
ValVue 2.4 Lite
ValVue 2.4 Lite software is shipped with each SVI II for positioner
calibration and configuration. ValVue 2.4 Lite software is offered
without registration. It provides sufficient functionality to fully
commission, configure, and start up a positioner on a control valve.