A-1
A
Specifications and
References
Physical and
Operational
Specifications
This section provides the physical and operational specifications for the
SVI II AP.
Table 8 Environmental Specifications
Operating Temperature Limits
-58 deg. F to 185 deg. F (-50 deg. C to 85 deg. C)
Storage Temperature Limits
-58 deg. F to 200 deg. F (-50 deg. C to 93 deg. C)
Temperature Effect
< 0.005% / deg. F typical; -40 deg. F to 180 deg. F (<
0.01% / deg. C typical; -40 deg. C to 82 deg. C)
Supply Pressure Effect
0.05% per psi (.73% per bar)
Relative Humidity
10 to 90% non-condensing
Humidity Effect
Less than 0.2% after 2 days at 104 F (40 deg. C), 95% Rel-
ative Humidity.
Insulation Resistance
Greater than 10 G Ohms at 50% RH.
MTBF
49 years based on MIL handbook calculation for electronic
parts and field data on mechanical parts
Electromagnetic Compatibility
Electrostatic
Electrostatic discharge — No effect with contact discharge
level of 4KV and air discharge level of 8 KV
(IEC 1000-4-2)
Radio frequency interference — Less than 0.2% at 10 volts
per meter (EN 50140)
Fast Transient Burst
No effect at 2 KV (Coupling clamp IEC 1000-4-4).
Vibration Influence
Measured at SVI II AP Housing
4 mm at 5 - 15 Hz - Negligible
2 G at 15 - 150 Hz Less than 2 % of span
1 G at 150 - 2000 Hz - Less than 2 % of span
Magnetic Field Influence
Negligible at 30 A/m (EN61000-4-8)
CE MARK certified to EN50081-2 and EN50082-2
Содержание Masoneilan SVI II AP-2
Страница 1: ......
Страница 8: ...Masoneilan Dresser SVI II AP Quick Start Guide vi ...