Check Out, Configuration and Calibration
Calibration
31
Check-out with a HART Handheld Communicator
If the SVI II AP is not equipped with optional push buttons and local
display the checkout and configuration is performed using the standard
HART communications interface.
C
onnect the HART Handheld Communicator (HHC) to the SVI II AP as
shown in Figure 14 below. Refer to the Product Manual for The HART
Communicator included with the HHC375 or other HART
Communication devices.
+
-
12.00 mA
Configuration
Lock Jumper
Input Signal
HHC375
Figure 14
SVI II AP HART Communicator Connections
Be sure that the configuration lock jumper is in the unlock position.
When the jumper is in the lock position (shorting the two-pin header) the
HHC375 is not permitted to make any changes. However, parameters
are readable. If fault messages appear, they must be handled before
proceeding with HART communications. Before communications
proceeds all error messages must be cleared. For example, the
following message is displayed if the instrument has been serviced and
the air is not connected.
Note:
“
Process applied to the non-primary variable is outside the
operating limits of the field device”