17.1. S1/S2 control – set-point configuration
Note
S1 refers to relay 1, S2 to relay 2.
Note
Although the description always refers to S1, the procedure for S2 is the same.
Note
If S1 was configured as 3-point controller, S2 cannot be used, since relay 2 is
used for S1.
In the menu CONTROL select the symbol S1 CONTROL. Here you
can set the following parameters:
Set point
Define which value the measured value should reach.
Type
Choose between on/off, P, PI, PID, and 3-point controller. This selection
defines the parameters displayed in this menu and in CONFIG. Only
those parameters relevant for the selected controller are shown.
Note
To help you with the configuration, Neon only shows those parameters
relevant for your controller choice. Same for the CONFIG menu which shows
only the required information.