36
User Analogs
10.10
The NetGuardian LPG Controller's 4 analog inputs measure continuous ranges of voltage. Analog alarms are
typically used to monitor propane tank level readings. To configure a user analog, simply fill in your description,
thresholds, and other fields listed in the table below, then click
Save
.
Note:
An analog channel must be enabled for it to be analyzed by the automation process.
The Provisioning > User Analogs menu
User Analogs
Default monitoring to
gauge view
Checking this box sets the default view in the
Monitor>User Analogs
menu to the gauge
view.
Enab (Enable)
Checking the box in the
Enab
column enables monitoring of the analog channel.
Description
User-definable description for the analog channel
Rev
Checking the reverse button changes negative values to positive, and positive values to
negative.
Notifications
Check which notification device(s), 1 through 8, you want to send alarm notifications for
this analog input.
Details
Record Freq
The frequency with which the NetGuardian will record the analog reading.
Deadband
The additional qualifying value the NetGuardian requires above/below your alarm thresholds
in order to set an alarm.
Units
The unit(s) of measurement reported by a connected analog input.