background image

39

Blue

 - The sensor is not supported by the NetGuardian LPG Controller.

To reconfigure or disable the Sensor ID, simply delete any data in this field and click 

Save

.

The unit will refresh the sensor ID on that channel.

Description

User-definable description for the sensor channel.

Parse

Checks to see if the

 Description

 field contains a valid equation.

Notification Devices

Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.

Advanced Sensor Configuration (Details>>)

Record Freq

The amount of time, in minutes (min) or seconds (s), between each recorded sensor
value.

Deadband

The amount (in native units) that the channel needs to go above or below a threshold
in order to cause an alarm.

Qual Time (Qualification

Time)

The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.

Qual. Type (Qualification

Type)

Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.

Thresholds

These settings are set to indicate the severity of the alarm depending on which
threshold values have been passed.  Enter values for Major Under (MjU), Minor Under
(MnU), Minor Over (MnO), and Major Over (MjO).

Post On

Select the threshold alarms to post. All thresholds, Major Only, Minor Only, Mojor
Over Only, Major Under Only.

Analog Gauge Type

Select the color-coded gauge that best represents your data.  Selecting 

None

 will

disable the analog gauge and only a numerical representation of the value will be
displayed  under 

Monitor 

Sensors

.

Note: 

Before plugging in any additional D-Wire Sensors, set up the internal sensor.

Script Sensors

A Script Sensor can be setup by entering a script type in the sensor ID field. The following types are currently
supported:

~count

 - The equation will be evaluated continuously.  If the evaluation changes at any point, the sensor's value

increases by an increment of 1.  This mode can be useful for counting the number of times a discrete input
toggles.

Evaluation Sensor; every tenth of a minute (6 seconds).
~evalMt 

-  The equation is evaluated every 6 seconds and its result becomes the sensor's value.

Evaluation Sensor; every minute.
~evalMn

 -  The equation is evaluated every 60 seconds and its result becomes the sensor's value.

Interval counter.

Interval Sensor
~intCnt

 - Sensor value will increment when the associated input's pulse length (high or low) is within a set

interval.  Example:  D5  V1 0 0 0 > V6 0 0 0 0 <  means the sensor value will increment when a 1ms to 60ms pulse
is detected on Discrete Input 5. This is useful for frequency detection/tracking.

A Script Sensor is configured to evaluate Reverse Polish Notation equations. A data token in an equation can
represent a discrete alarm, analog reading, sensor reading, relay status, system alarm status, or a constant value. 
The format for a token in an equation must be a data type followed by an index (for example: Discrete Input 1 in an
equation would be represented as "d1", Analog Channel 3 would be "a3", etc.).  Each token is typically followed by
another token or an operator.  The equations are entered in the description field for the Script Sensor.

Содержание NetGuardian LPG D-PK-NGLPG

Страница 1: ...USER MANUAL NetGuardian LPG Controller February 15 2019 Visit our website at www dpstelecom com for the latest PDFmanual and FAQs Firmware Version 1 0A D PK NGLPG D UM NGLPG...

Страница 2: ...or used to make a derivative work by either mechanical electronic or any other means in whole or in part without prior written consent fromDPS Telecom except as required by United States copyright law...

Страница 3: ...sors 6 3 10 Generator 6 4 10 Quick Start How to Connect to the NetGuardian LPG Controller 7 11 via Craft Port using TTY Interface 7 1 11 via LAN 7 2 17 TTY Interface 8 18 Configure Serial Port via TTY...

Страница 4: ...rgets 11 6 49 System Alarms 11 7 50 Graph 11 8 51 Device Access Descriptions 12 53 Backup Configuration 13 54 Firmware Upgrade 14 55 Reference Section 15 56 Display Mapping 15 1 56 System Alarms 15 2...

Страница 5: ...n override feature so that a tech can manually turn on and off valves through the web browser interface The NetGuardian LPG Controller has an indicator LED for each tank showing valve status open clos...

Страница 6: ...Output Fuse None Valve Control Voltage Output 24 VDC Output Current 0 75Amax per output 3Atotal Operating Temp 32 to 140 F 0 to 60 C Output Fuse 5 Amp GMT 1 Industrial Operating Temp 22 to 158 F 30 to...

Страница 7: ...re designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energ...

Страница 8: ...nd call DPS Telecom at 1 800 622 3314 NetGuardian LPG Controller NetGuardian LPG Controller D PK NGLPG Resource CD NetGuardian LPG Controller User Manual 6 ft USB Download Cable D UM NGLPG D PR 046 10...

Страница 9: ...5 x4 x6 3 Point Locking Terminal 2 Point Locking Terminal 2 821 10335 00 2 821 10235 00 x 1 Lg Power Connector Main Pwr 2 820 00862 02...

Страница 10: ...ews Pads 1 000 12500 06 2 015 00030 00 14ft Ethernet Cable D PR 932 10B 14 Optional Shipping Items Available by Request 3 1 Temp Sensor Temp Humidity Sensor D PK DSNSR 12001 D PK DSNSR 12002 Small WAG...

Страница 11: ...e flush or rear mounted The NetGuardian LPG Controller mounts in a 19 rack or a 23 rack using the provided rack ears for each size Two rack ear locations are provided Attach the appropriate rack ears...

Страница 12: ...ng Red Data Received over USB Lnk Solid Green LAN Connected Off LAN Not Connected LAN Flashing Yellow Activity over Ethernet Connection Off No Activity 100BT Solid Green LAN Connection Speed is 100Bas...

Страница 13: ...right terminal is Ground and its left terminal is Battery Lead 4 Insert a battery ground into the power connector plug s right terminal GND and tighten the screw 5 Insert a battery lead to the plug s...

Страница 14: ...n each of the 4 propane tanks Tank Level Sensors 6 3 The Tank Level Sensor Inputs on the NetGuardian LPG Controller The Tank Level Sensor inputs monitor the fuel levels in the tanks They supply 5V for...

Страница 15: ...using TTY Interface 7 1 NetGuardian LPG Controller Craft Port Use the front panel craft port to connect the NetGuardian LPG Controller IT to a PC for onsite unit configuration To use the craft port c...

Страница 16: ...Select Install from a list or specific location Advanced 3 Click Next 4 Select Search for the best driver in these locations 5 Insert NetGuardian LPG Controller Resource Disc CD into your PC 6 Click B...

Страница 17: ...ng message will confirm installation of a new USB Communications Port 8 Click Finish to close the Wizard Now that the driver has been installed a new COM port is being emulated on your PC Before using...

Страница 18: ...14 9 Right click the My Computer icon on your desktop then click Manage 10 Click Device Manager in the left pane...

Страница 19: ...k on the Start menu select Programs Accessories Communications HyperTerminal 13 At the Connection Description screen enter a name for this connection You may also select an icon The name and icon do n...

Страница 20: ...ou are using on your PC and make sure you are using the cable provided Additional cables can be ordered from DPS Telecom 17 The NetGuardian LPG Controller s main menu will appear Type C for C onfig th...

Страница 21: ...t 2 Look up your PC s current IP address and subnet mask and write this information down 3 Reset your PC s IP address to 192 168 1 200 Contact your IT department if you are unsure how to do this 4 Res...

Страница 22: ...etup Telnet sessions are established at port 2002 not the standard Telnet port as an added security measure If you re using Windows 7 then you ll need to install telnet before you can use the TTY inte...

Страница 23: ...Type 232 485 Baud 9600 57600 19200 9600 4800 2400 1200 Parity None even odd Stop bits 1 2 3 Set the RTS head tail Carrier time Suggested settings are 0 0 if using RS232 Quick Turn Up 9 The next secti...

Страница 24: ...ication Setting screen use the drop down box to set what events to use for this notification Now select the Send Email Notification button and click Save and Next 3 At the Email Notification screen yo...

Страница 25: ...test the email notification you ve just setup you will prompted with a pop up Click OK to send a test email alarm notification Confirm all your settings by checking your email to see if you ve receiv...

Страница 26: ...sure we ve made our default dps_public 2 Click on the Notifications button in the Provisioning menu You can setup as many as 8 different notifications Begin the setup wizard by clicking Edit for a not...

Страница 27: ...different hours on the weekend Use the check boxes to select the days of the week and select the time from the drop down menus Click Save and Finish To try a test notification click the Test button S...

Страница 28: ...nges locally The web interface will then prompt you to either Write your changes to the unit or Reboot the unit for changes to take effect in the top left corner of your browser The relevant options w...

Страница 29: ...G Controller unit Optional field DCP Responder Settings For use with T Mon DCP Unit ID User definable ID number for the target unit DCP Address DCP Unit Protocol Drop down menu of available protocols...

Страница 30: ...user profiles and password information Write Config change unit configuration Enables the user to change the unit config by accessing the Write feature in the control menu View monitor pages Allows t...

Страница 31: ...DHCP means the unit will NOT operate in a T Mon environment Unit IP IP address of the NetGuardian LPG Controller Subnet Mask A road sign to the NetGuardian LPG Controller telling it whether your pack...

Страница 32: ...any times the RADIUS server will retry a logon attempt Time out Enter in the number of seconds before a logon request is timed out Servers 1 2 IPA Enter the IP address of the RADIUS server Port Port 1...

Страница 33: ...requests Read and Write Access This field defines how the NetGuardian LPG Controller unit may be accessed via SNMP This can be set to the following Access Disabled Restricts all access to unit via SN...

Страница 34: ...with Gmail To send with Gmail SMTP server do the following SMTP Server IP or Host Name should be set to smtp gmail com Port number must be set to 465 SMTP authentication radio button must be selected...

Страница 35: ...chedule The notifications scheduling menu is where you will tell the NetGuardian LPG Controller exactly which days and times you want to receive alarm notifications You set 2 different schedules for e...

Страница 36: ...ings are pulled into one easy to configure layout LPG Automation Settings Enable Automation When checked enables automation process to open or close the tank valves LPG Tanks Number of tanks that the...

Страница 37: ...t the NetGuardian to set an alarm Recorded values less than an under value or greater than an over value will cause alarms Post On Select the threshold alarms to post All thresholds Major Only Minor O...

Страница 38: ...evice s 1 through 8 you want to send alarm notifications for that alarm point Advanced Alarm Configuration Advanced On Set User definable description condition that will appear for the discrete alarm...

Страница 39: ...ontroller s control relay Momentary Time Control on time in milliseconds when you execute the MOM command Max limit of 600 seconds When latched status string Description to display when control is lat...

Страница 40: ...view in the Monitor User Analogs menu to the gauge view Enab Enable Checking the box in the Enab column enables monitoring of the analog channel Description User definable description for the analog c...

Страница 41: ...over value will cause alarms Post On Select the threshold alarms to post All thresholds Major Only Minor Only Major Over Only Major Under Only Enable Checking this box enables Push to Talk feature for...

Страница 42: ...sensors can be accomplished from the Provisioning Sensors menu From this screen you can configure D Wire sensors select notification devices and set thresholds The Provisioning Sensors menu Basic Sens...

Страница 43: ...and only a numerical representation of the value will be displayed under Monitor Sensors Note Before plugging in any additional D Wire Sensors set up the internal sensor Script Sensors A Script Sensor...

Страница 44: ...tor is found the previous 2 values are popped from the stack and are used to perform the operation the first item popped is the SECOND operand The result of the operation is then pushed onto the stack...

Страница 45: ...ng Targets menu Provisioning Ping Targets ID ID number for the ping target Enab Check this box to enable the ping target Description User definable description for the ping target Server IP or Hostnam...

Страница 46: ...stem Alarms menu Editing System Alarms Pnt Point The system alarm point number Description Non editable description for this System housekeeping Alarm Silence Check this box to choose to silence this...

Страница 47: ...43 Timers 10 14 Enter the amount of time in seconds sec or minutes m in each value field and click Save The Provisioning Timers menu...

Страница 48: ...or host name then click Sync Example us pool ntp org Note Make sure to configure DNS before using host name instead of IP address Time Zone Select your time zone from the drop down menu Adjust Clock...

Страница 49: ...ened or closed Tank Level Tank level reading Status status of the tank level compared to the other tank levels in the automation process Alarms 11 2 This selection provides the status of the base alar...

Страница 50: ...ed The control state Released means the LPG valve is open View and operate control relays from the Monitor Controls menu Control Relay Operation ID ID number for the control relay Description Descript...

Страница 51: ...tion of each analog channel the current reading the units being read and alarm conditions major under minor under major over minor over according to your temperature settings If configured under Provi...

Страница 52: ...for minor alarms or red for major alarms Fig 12 5 Current status of all analog inputs in the Monitor User Analogs in Table View Fig 12 6 Current status of all analog inputs in the Monitor User Analog...

Страница 53: ...6 Ping Targets can be viewed by going to Monitor Ping Targets Here you can view the state either Clear or Alarm for each of your configured Ping Targets View the status of Ping Targets from the Monito...

Страница 54: ...he system alarms by indicating if an alarm has been triggered Under the State column the status will appear in red if an alarm has been activated The status will be displayed in green when the alarm c...

Страница 55: ...trending values To create your Graph specify the Channel Analogs 1 5 or Sensors 1 16 Group Interval 1 120 minutes hours days or weeks the Group Function Average Min Max and Start End Times Once you ha...

Страница 56: ...e over the lines to quickly view measurements date time and value within their context of the overall graphing trend Below the graph is a full textual list of all indexed points with their dates and v...

Страница 57: ...Description Backup Config Backs up the units configuration settings Read Reads a configuration file from the unit Write Commits all changes made in the web interface to the NetGuardian LPG Controller...

Страница 58: ...web browser download the file to your desktop or other location on your computer 3 Now your configuration should be saved If you need to upload a configuration follow the steps below To upload your co...

Страница 59: ...reen click the Restore Configuration link located in the System Controls section To upload firmware click on Upload on the top right corner of the web interface At the Firmware Load screen simply brow...

Страница 60: ...fication 6 failed 99 1 46 Notification 7 failed 99 1 47 Notification 8 failed 99 1 48 NTP failed 99 1 49 Timed tick 99 1 50 Serial 1 RcvQ full 99 1 51 Dynamic memory full 99 1 52 Unit reset 99 1 53 DC...

Страница 61: ...Level 4 Minor Over 99 1 34 Tank Level 4 Major Under 99 1 35 Tank Level 4 Major Over 99 1 36 Control 99 1 41 48 Value 99 1 49 64 Display 5 Analog 5 Minor Under 99 1 1 Analog 5 Minor Over 99 1 2 Analog...

Страница 62: ...tal sensor 2 Sensor not detected 99 1 37 Control 99 1 41 48 Value 99 1 49 64 Display 7 Digital Sensor 1 Minor Under 3 Alarm Module Alarm 1 AC Fail Module 99 1 1 Digital Sensor 1 Minor Over 3 Alarm Mod...

Страница 63: ...rm 2 99 1 2 Digital Sensor 5 Major Under 3 Alarm Module Alarm 3 99 1 3 Digital Sensor 5 Major Over 99 1 4 Digital Sensor 5 Sensor Not Detected 99 1 5 Control 99 1 9 16 Value 99 1 17 32 Digital Sensor...

Страница 64: ...60 Module Alarm 3 Digital Sensor 8 Major Over 99 1 36 Digital Sensor 8 Sensor Not Detected 99 1 37 Control 99 1 41 48 Value 99 1 49 64 Display Mapping...

Страница 65: ...99 1 2 Digital Sensor 11 Major Under 3 Alarm Module Alarm 3 99 1 3 Digital Sensor 11 Major Over 99 1 4 Digital Sensor 11 Sensor Not Detected 99 1 5 Control 99 1 9 16 Value 99 1 17 32 Digital Sensor 1...

Страница 66: ...62 Module Alarm 3 Digital Sensor 14 Major Over 99 1 36 Digital Sensor 14 Sensor Not Detected 99 1 37 Control 99 1 41 48 Value 99 1 49 64 Display Mapping...

Страница 67: ...m 2 99 1 2 Digital Sensor 17 Major Under 3 Alarm Module Alarm 3 99 1 3 Digital Sensor 17 Major Over 99 1 4 Digital Sensor 17 Sensor Not Detected 99 1 5 Control 99 1 9 16 Value 99 1 17 32 Digital Senso...

Страница 68: ...64 Module Alarm 3 Digital Sensor 20 Major Over 99 1 36 Digital Sensor 20 Sensor Not Detected 99 1 37 Control 99 1 41 48 Value 99 1 49 64 Display Mapping...

Страница 69: ...m 2 99 1 2 Digital Sensor 23 Major Under 3 Alarm Module Alarm 3 99 1 3 Digital Sensor 23 Major Over 99 1 4 Digital Sensor 23 Sensor Not Detected 99 1 5 Control 99 1 9 16 Value 99 1 17 32 Digital Senso...

Страница 70: ...66 Module Alarm 3 Digital Sensor 26 Major Over 99 1 36 Digital Sensor 26 Sensor Not Detected 99 1 37 Control 99 1 41 48 Value 99 1 49 64 Display Mapping...

Страница 71: ...m 2 99 1 2 Digital Sensor 29 Major Under 3 Alarm Module Alarm 3 99 1 3 Digital Sensor 29 Major Over 99 1 4 Digital Sensor 29 Sensor Not Detected 99 1 5 Control 99 1 9 16 Value 99 1 17 32 Digital Senso...

Страница 72: ...IP Address Not Set 37 LAN hardware error 38 SNMP Process Error 39 SNMP Community Error 40 LAN TX packet drop 41 Notification 1 Failed 42 Notification 2 Failed 43 Notification 3 Failed 44 Notification...

Страница 73: ...Grid 3 the Display 3 Tbl B1 O _OV_Traps points _OV_vTraps 1 3 6 1 4 1 2682 1 2 0 PointSet 20 PointClr 21 SumPSet 101 SumPClr 102 ComFailed 103 ComRestored 014 P0001Set 10001 through P0064Set 10064 P00...

Страница 74: ...70 AState 6 For specific alarm points see Table B6...

Страница 75: ...Description 0 Version Public Request Trap Request 1 3 6 1 4 1 2682 1 4 Enterprise 126 10 230 181 Agent address Enterprise Specific Generic Trap 8001 Specific Trap 617077 Time stamp 1 3 7 1 2 1 1 1 0...

Страница 76: ...to configure the unit IP address the subnet mask and the default gateway A sample configuration could look like this Unit Address 192 168 1 100 subnet mask 255 255 255 0 Default Gateway 192 168 1 1 Sa...

Страница 77: ...ovide SNMP managers with a single MIB for all DPS Telecom products Q How many traps are triggered when a single point is set or cleared The MIB defines traps like major alarm set cleared RTU point set...

Страница 78: ...rmation when you call our Technical Support representatives can assist you in gathering it Please write the information down for easy access Please have your user manual and hardware serial number rea...

Страница 79: ...75...

Страница 80: ...old it harmless for and against any and all claims damages losses costs expenses obligations liabilities fees and costs and all amounts paid in settlement of any claim action or suit which may be asse...

Страница 81: ...lightning unless and to the extent that the product specification provides for resistance to a defined disaster e damage caused by unauthorized attachments or modifications f damage during shipment fr...

Страница 82: ...ct manuals Product datasheets Exclusive user forms Expert tips on using your alarm monitoring equipment advanced techniques that will save you hours of work Educational White Papers deliver fast infor...

Отзывы: