The Provisioning > Alarms menu
Basic Alarm Configuration
ID
Alarm ID number.
Description
User-definable description for the discrete alarm point.
Rev (Reverse)
Reverse: Check this box to reverse the polarity of the alarm point. Leaving this option
un-checked means a normally open contact closure is an alarm. When polarity is
reversed, a normally closed alarm point is clear when closed.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Alarm Configuration (Advanced>>)
On Set
User-definable description (condition) that will appear for the discrete alarm input on
Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the discrete alarm input on
Clear: "Example: "Alarm Cleared".
Qual. Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.