T
ECHNICAL
D
ATA
Housing:
Self extinguishing ABS
Case:
Front panel 32x74 mm, depth 60mm
Mounting :
29x71 mm panel cut-out
Frontal protection:
IP65
Connections:
Removable terminal block 12 and 14 ways
Power supply:
12Vac/dc
±
10%, 24Vac/dc
±
10%, 50-60Hz
Power absorption:
5VA max
Inputs:
4 NTC probes,or 3 NTC probes and one 4..20mA / 0..10V
Digital inputs
: 5 free voltage
Relay outputs:
4 / 5 relays (depending on the model) SPDT 5(3)A, 250Vac
Open collector:
12V, 40mA
Analogue output:
4..20mA / 0..10V
Serial output :
TTL standard
Communication protocol:
Modbus – RTU
Data storing:
on the non-volatile memory (EEPROM)
Kind of action:
1B
Pollution grade:
normal
Software class:
A
Operating temperature:
0÷60 °C
Storage temperature:
-25÷60 °C
Relative humidity:
20
÷
85% (no condensing)
Measuring range:
NTC probe
-40÷110°C C (- 40 ÷ 230 °F)
Measuring range:
pressure trasducers
0÷ 50 bar
Temperature resolution:
0,1 °C or 1°C
Accuracy (ambient temp. 25°C)
: ±0,5 °C ±1 digit
Input/output
Tipo
Probes
Pb1, Pb2 e Pb4
Configurable: NTC, Digital input
Pb3
Configurable: NTC, 4..20mA, 0..5V
Digital inputs
ID1, ID2 e ID5
Configurable; free voltage
ID3
High pressure; free voltage
ID4
Low pressure; free voltage
Relays
RL1
For compressor: relay SPDT 5(3) A 250Vac
RL2, RL3, RL4 e RL5
Configurable: relè SPDT 5(3) A 250Vac
PWM output / open collector
PWM: modulation of the evaporator fan, open collector:
configurable
Open collector output
Configurab\le; 12 Vcc 40mA max
4..20mA or 0..10V output
Modulation of the evaporator fan or modulation of the evaporator
pump
Hot Key / TTL output
Output for Hot Key or Persional computer / supervisor systems
Remote keyboard
Output for remote keyboard
Dixell
s.r.l. Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13