IC100CX
1592022550
Quick reference guide IC100CX GB rel.1.0 03/03/2008 Page 28 di 39
CF32
Celsius or Fahrenheit selection
0= °C / °BAR
1= °F / °psi
0
1
CF33
Power supply frequency
0= 50 Hz
1= 60 Hz
2 = DC power supply (PWM configrured as output for an
external alarm relay)
0
2
CF34
Serial Address for monitoring
1
247
CF35
Remote terminal keyboard
0= Not used
1= 6 keys
2= 6 keys with NTC probe mounted on board
0
2
CF36
Default viewing of upper display of the controller
0 = PB1 visualization
1 = PB2 visualization
2 = No visualization
3 = PB4 visualization
4 = Real working set point (set point modified from Energy
Saving, Dynamic set point, function for units without water
storage tank)
5 = Unit status
6 = No visualization
7 = No visualization
8 = Working differential
9 = Unit set point (parameter value)
0
8
CF37
Firmware Release
CF38
Eeprom – Parameter mapping
CF39
RL2 configuration
0 = Alarm relay
1 = compressor 1 capacity step
2 = compressor 2
3 = ON/OFF ventilation
4 = reversing valve
5 = anti-freezer heaters / integration heater n.1
6 = solenoid valve on water circuit
7 = solenoid valve on water circuit only for heat pump
8= anti-freezer heaters / integration heater n. 2
9 = evaporator water pump
/ supply fan (air / air unit)
10= condenser water pump
0
10
CF40
RL3 configuration
0 = Alarm relay
1 = compressor 1 capacity step
2 = compressor 2
3 = ON/OFF ventilation
4 = reversing valve
5 = anti-freezer heaters / integration heater n.1
6 = solenoid valve on water circuit
7 = solenoid valve on water circuit only for heat pump
8= anti-freezer heaters / integration heater n. 2
9 = evaporator water pump
/ supply fan (air / air unit)
10= condenser water pump
0
10