IC100CX
1592022550
Quick reference guide IC100CX GB rel.1.0 03/03/2008 Page 32 di 39
CO27
Delay between condenser pump shutdown and compressor
shutdown
0
250
Sec
CO28
SET hour counter of water condenser pump
0
999
Hr
10 Hr
Compressors in tandem mode
CO29
Maximum continuous operating time of a compressor
0
250
Min
CO30
Compressor start-up delay after activation of the water
solenoid valve
0
250
sec
10 Sec
Modulating evaporator water pump
CO31
Peak time of modulating pump at maximum speed required
by regulation
0
250
sec
CO32
Minimum speed % of modulating pump in operation with
enabled compressor (Chiller)
30
100
%
CO33
Minimum speed % of modulating pump in operation with
enabled compressor (Heat Pump)
30
100
%
CO34
Speed % of modulating pump in operation with enabled
compressor
30
100
%
CO35
Set point modulating pump in chiller mode (evaporator outlet
temperature)
-50.0
-58
110
230
°C
°F
Dec
int
CO36
Temperature control band for the modulating pump in chiller
function
0.0
0
25.0
45
°C
°F
Dec
int
CO37
Delay for switching off compressor by heat regulation with
water pump < 100 % in chiller function
0
250
sec
CO38
Set point modulating pump in heat pump mode (evaporator
outlet temperature)
-50.0
-58
110
230
°C
°F
Dec
int
CO39
Temperature control band for the modulating pump in heat
pump function
0.0
0
25.0
45
°C
°F
Dec
int
CO40
Delay for switching off compressor by regulation with water
pump < 100 % in HP function
0
250
sec
Pr2
Password
0
999
Condenser Fan control parameter
Parameter
Description
Min
Max
Meas.
Resolution
FA01
Fan output
0= Not enabled
1= Enabled
0
1
FA02
Fan regulation
0= On when compressor On
1= ON / OFF
2= Proportional speed control
0
2
FA03
Fan related to compressor
0= With compressor
1= Independent from compressor
0
1
FA04
Maximum speed time when the fan starting
0
250
Sec
FA05
Phase difference fan
0
20
Micro
Sec
250
µ
s
FA06
Not used
FA07
Cooling pre-ventilation before ON compressor
0
250
Sec
FA08
Minimum fan speed in summer
30
100
%
FA09
Maximum fan speed in summer
30
100
%