IC100CX
1592022550
Quick reference guide IC100CX GB rel.1.0 03/03/2008 Page 37 di 39
Parameter
Description
Min
Max
Meas.
Resolution
AL01
Low pressure alarm delay time
0
250
Sec
AL02
Maximum low pressure alarm events in 1 hour
0
16
AL03
Low pressure alarm with off compressor
0= Not enabled when compressor Off
1= Enabled when compressor Off
0
1
AL04
“Water flow/Supply fan thermal protection” alarm delay after
“water pump / supply air fan” starting.
0
250
Sec
AL05
Maximum duration of the flow switch alarm before it
becomes manual and blocks the water pump
0
250
Sec
AL06
“Water flow/Supply fan thermal protection” input activation
duration
0
250
Sec
AL07
“Water flow/Supply fan thermal protection” input de-
activation duration
0
250
Sec
AL08
Thermal protection alarm delay after starting the compressor
0
250
Sec
AL09
Number of maximum thermal protection alarm events.
0
16
AL10
Maximum number of high temperature / condenser pressure
alarm interventions per hour
0
16
AL11
Condensing temperature/pressure high alarm setpoint for
input probe
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL12
Temperature/pressure high alarm differential for input probe
0
0
0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL13
Low pressure alarm delay for input probe
0
250
Sec
AL14
Low pressure alarm Setpoint for input probe
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL15
Low pressure differential for input probe
0
0
0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL16
Maximum number of the low alarm events in 1 hour for input
probe
0
16
AL17
Alarm relay and buzzer activation when the unit is Off or
stand-by
0= Alarm relay and buzzer enabled
1= Alarm relay and buzzer disabled
0
1
AL18
Alarm relay output/open collector polarity
0= Output without voltage in normal conditions, with voltage
when there is an alarm
1= Output with voltage in normal conditions, without voltage
when there is an alarm
0
1