IC100CX
1592022550
Quick reference guide IC100CX GB rel.1.0 03/03/2008 Page 31 di 39
CO04
OFF delay time between two compressors or Comp. and
valve
0
250
Sec
CO05
Output time delay after power supply start-up
0
250
Sec
10Sec
CO06
Compressor On delay time after Pump/”Supply fan”
activation
1
250
Sec
CO07
Compressor OFF delay time after Pump/”Supply fan” de-
activation
0
250
Sec
CO08
Compressor rotating control
0= Enabled
1= Fixed sequence
0
1
CO09
Time delay for solenoid valve of water side (CF39)
0
250
Sec
CO10
Stage vale polarity
0= Capacity stage ON
1= Capacity stage OFF
0
1
CO11
Water pump / Supply fan operating mode
0= Not used
1= Always on (ON/OFF output)
2= ON if the compressor is on (ON/OFF output)
3= Always on (4
÷
20mA output)
4= ON if compressor is ON (4
÷
20mA output)
0
4
CO12
Compressor 1
0 = Enabled
1 = OFF
0
1
CO13
Compressor 2 / Stage valve.
0 = Enabled
1= OFF
0
1
CO14
Hour counter setpoint for 1
st
compressor
0
999
Hr
10 Hr
CO15
Hour counter setpoint for 2
nd
compressor
0
999
Hr
10 Hr
CO16
Hour counter setpoint for pump/”Supply fan”
0
999
Hr
10 Hr
Unloading evaporator
CO17
Unloading set point (evaporator side)
0
32
110
230
°C
°F
Dec
int
CO18
Unloading Differential (evaporator side)
0.1
0
25.0
45
°C
°F
Dec
int
CO19
Delay unloading function (evaporator side)
0
250
Sec
10 Sec
CO20
Maximum unloading operation time in case of high
evaporator temperature
0
250
Sec
10 Sec
Unloading condenser
CO21
Unloading pressure set point in chiller mode (condenser
side)
0.0
0
50.0
725
Bar
Psi
Dec
int
CO22
Unloading pressure differential in chiller mode (condenser
side)
0.0
0
12
174
Bar
Psi
Dec
int
CO23
Unloading pressure set point in heat pump mode
(condenser side)
0.0
0
50.0
725
Bar
Psi
Dec
int
CO24
Unloading pressure differential in heat pump mode
(condenser side)
0.0
0
12
174
Bar
Psi
Dec
int
CO25
Maximum unloading operation time in condenser side
0
250
Sec
10 Sec
Water pump condenser
CO26
Condenser water pump operating mode
0= Not used
1= Continuous opeartion
2= Only for compressor demand
0
2