IC100CX
1592022550
Quick reference guide IC100CX GB rel.1.0 03/03/2008 Page 34 di 39
FA25
Hot Start Setpoint
-50.0
-58
110
230
°C
°F
Decimal
integer
FA26
Hot Start differential
0.0
0
25.0
45
°C
°F
Decimal
integer
Pr2
Password
0
999
Anti-freeze / Heater parameters
Parameter
Description
Min
Max
Meas.
Resolution
Ar01
Minimum value of Anti-Freeze Setpoint
-50.0
-58
Ar03
°C
°F
Decimal
integer
Ar02
Maximum value of Anti-Freeze Setpoint
Ar03
110
230
°C
°F
Decimal
integer
Ar03
Anti-freeze Setpoint in chiller mode
Ar01
Ar02
°C/°F
Dec/int
Ar04
Anti-Freeze Differential in chiller mode
0
0
25.0
45
°C
°F
Decimal
integer
Ar05
Anti-Freeze alarm delay
0
250
Sec
Ar06
Maximum number of Anti-Freeze alarm events in 1 hour
0
16
Ar07
Anti-Freeze alarm delay after starting in Heat Pump
0
250
Sec
Ar08
Anti-Freeze Setpoint of the electrical heater in Chiller mode
-50.0
-58
110
230
°C
°F
Decimal
integer
Ar09
Anti-Freeze Setpoint of the electrical heater in Heat Pump
mode
-50.0
-58
110
230
°C
°F
Decimal
integer
Ar10
Anti-Freeze Setpoint of external electrical heater
(water/water units)
-50.0
-58
110
230
°C
°F
Decimal
integer
Ar11
Anti-Freeze Differential in Chiller
0
0
25.0
45
°C
°F
Decimal
integer
Ar12
Anti-Freeze Differential in Heat Pump
0
0
25.0
45
°C
°F
Decimal
integer
Ar13
Anti-freeze electrical heater regulation
0= enabled during regulation control
1= enabled active during regulation an defrost
0
1
Ar14
Anti-freeze electrical heater regulation in Chiller mode
0= OFF in chiller
1= ON in chiller
0
1
Ar15
Anti-freeze electrical heater regulation in H.P. mode
0= OFF in Heat Pump
1= ON in Heat Pump
0
1
Ar16
Anti-freeze control probe in Chiller mode
0= Pb1
1= Pb2
2= PB3 probe control
3= PB4 probe control
0
3
Ar17
Anti-freeze control probe in Heat Pump mode
0= Pb1
1= Pb2
2= PB3 probe control
3= PB4 probe control
0
3