IC100CX
1592022550
Quick reference guide IC100CX GB rel.1.0 03/03/2008 Page 30 di 39
CF46
Controller: visualization in Std-by mode
0 = default visualization (CF36 and CF43 parameters)
1 = the display visualizes “OFF”
2 = the display visualizes “StbY”
0
2
CF47
Remote keyboard: visualization in Std-by mode
0 = default visualization (CF36 and CF43 parameters)
1 = the display visualizes “OFF”
2 = the display visualizes “StbY”
0
2
CF48
Analog output configuration
0 = 4..20mA
1 = 0..10V
0
1
Pr2
Password value
0
999
Dynamic Setpoint
Parameter
Description
Min
Max
Meas
Resolution
Sd01
Dynamic Setpoint
0= Not enabled
1= Enabled
0
1
Sd02
Maximum summer dynamic Offset
- 30
-54
30
54
°C
°F
Decimal
integer
Sd03
Maximum winter dynamic Offset
- 30
-54
30
54
°C
°F
Decimal
integer
Sd04
External air d. setpoint during summer
-50.0
-58
110
230
°C
°F
Decimal
integer
Sd05
External air d. setpoint during winter
-50.0
-58
110
230
°C
°F
Decimal
integer
Sd06
External air differential during summer
- 30
-54
30
54
°C
°F
Decimal
integer
Sd07
External air differential during winter
- 30
-54
30
54
°C
°F
Decimal
integer
Pr2
Password value
0
999
Energy Saving
Parameter
Description
Min
Max
Meas
Resolution
ES01
Energy saving starting hour (0÷24)
0
23.50 Min
10 Min
ES02
Energy saving ending hour (0÷24)
0
23.50 Min
10 Min
ES03…ES09
Monday…Sunday
0 = Not enabled
1= Enabled
0
1
ES10
Energy saving setpoint offset in chiller
-30.0
-54
30.0
54
°C
°F
Decimal
integer
ES11
Energy saving differential in chiller
0.1
0
25.0
45
°C
°F
Decimal
integer
ES12
Energy saving setpoint offset in heat pump
-30.0
-54
30.0
54
°C
°F
Decimal
integer
ES13
Energy saving differential in heat pump
0.1
0
25.0
45
°C
°F
Decimal
integer
Pr2
Password value
0
999
Compressor parameters
Parameter
Description
Min
Max
Meas.
Resolution
CO01
Minimum ON time
0
250
Sec
10Sec
CO02
Minimum OFF time
0
250
Sec
10Sec
CO03
ON delay time between two compressors or Comp. and
valve
1
250
Sec