Components
Digitize Inc.
700226-0001 Rev. F 05/11
2-13
Q-Node Specifications
Digitize Part Number: 425183-0004
Dimensions: 2.75in. x 2.75in; Open PCB
Power Requirements: 10 – 14 VDC @ 300 milliamps max., Must be connected to a
Regulated Power Supply, UL Listed for Fire Protective Signaling
Systems (UL 1481).
Ports: 1 RS-232 Port
1 RS-485 Port
1 Firmware Programming Port
Operating Environment: Install in a dry, indoor environment.
Operating Temperature: 32°F-165°F
Operating Humidity: 0-95%, non-condensing
TBUSS Capacity: 99 ID Modules maximum.
TBUSS Length: Can be upto 5000’.
Inputs: 1 Tamper Input – Dry Contact
1 Low Battery Input – Dry Contact
1 AC Power Fail Input – Dry Contact
Outputs: 1 Form C Relay rated for 125 VAC
@ 0.6 amps, 2 amps @ 30 VDC.
Audible Indicator: Beeper mounted to pcb.
Indicators: 2 sets of six leds. One set on the component side of pcb, on set on the
solder side of the pcb. Leds indicate the presence of communication
on the RS-485 port, the RS-232 port and the TBUSS.
Approvals: ETL Approved