Advanced Settings & Options
Digitize Inc.
7-2
700226-0001 Rev. F 05/11
The SST SLOW relay will code out the same box number as the Q-IR or Q-I/O
device. Pressing the STOP key will abort both the SST SLOW and the SST to the Q-
Mux device. If you wish to transmit only via the SST SLOW (or FAST), use the @B
command in place of the @Q command. You may make multiple transmissions by
adding several @B or @Q (or any other supported @ commands) to the text screens.
Only one box transmission will be made at any one time.
For example, Zone 2 Alarm display reads:
Joe’s Hardware 1st Floor
@Q2-01-1234
This translates to: Node #2, Relay #01 will code 4 rounds for Box 1234
.