DigitAx User Guide
Issue code: dgxu4
11-5
Pr75
Pr76
Position Reference using
Serial Communications
R–W
16384
steps/rev
Def
.
val.
0
Res.
These two parameters permit serial communications
to be used to control the position reference
.
The
position reference value is [(
Pr76
×
1000) +
Pr75
]
.
Any changes to the values of
Pr75
and
Pr76
are
effective only after the values of
both
parameters
have been written.
Pr80
I
2
t Level
RO
0 to 100
%
Def
.
val.
Res.
0.1
Displays values corresponding to I
2
t accumulation
.
I
2
t limit is activated at 100%.
Pr81
Braking resistor protection
RO
0 to 1999.9
Def
.
val.
Res.
0.1
Displays a value proportional to the power
dissipated in the braking circuit
.
When
Pr81
reaches 100, parameter
b95
is set at 1.
Pr83
Rotor position
RO
0 to 2047
Def
.
val.
Res.
1
Shows the shaft position at all times.
Pr95
Number of Motor Poles
R–W
Def
.
val.
6
Res.
4, 6, or 8 poles can be set.
Pr97
Software version number
RO
Def
.
val.
Res.
(This manual applies to V4.XX.XX software.)
Pr98
Last alarm store
RO
Def
.
val.
Res.
Displays the cause of the last trip
.
Pr98
is cleared
when the Drive is reset by setting
b03
at 1
.
When
Pr98
is interrogated using Serial Communications, a
number representing the trip is transmitted
.
The
numbers are as follows:
No.
Condition
Trip code
0
Drive normal
1
Overvoltage
OV
2
Undervoltage
OU
3
Overcurrent
OC
4
Overtemperature
Oh
5
Resolver break
rb
6
I
2
t integrating
It
7
Temperature pre-alarm
PA
8
Overspeed
OS
9
Digital output short circuit
SC
10
External trip
Et
11
Internal fault
dOI or Err
Pr99
Full Scale Speed
R–W
200 to 3000
3200 to 6000
RPM
Def
.
val.
3000
Res.
200
400
11.2 Bit
parameters
b0
Enable change of security code
R–W
0 or 1
Def
.
val.
0
Res.
Set at 1 to enable the security code to be changed
to any valid number
.
Refer to
Pr25
.
b1
Recall last parameter settings
from
EEPROM
R–W
0 or 1
Def
.
val.
0
Res.
Return to the last-written parameter values
.
Set
b2
at 0 to allow parameter recall
.
The display will show
rEAd
during this process. Related to
b5
and
b99
.
b2
Drive enable
R–W
0 or 1
Def
.
val.
1
Res.
When
b2
= 0, the Drive is disabled.
When
b2
= 1, the Drive is enabled
.
Refer to terminal B14.
Содержание DBE1100S
Страница 3: ...User Guide DigitAx AC Servo Drive 1 4kW to 22kW Part Number 0415 0008 Issue Number 4...
Страница 8: ...DigitAx User Guide Issue code dgxu4 iv...
Страница 20: ...DigitAx User Guide Issue code dgxu4 3 8...
Страница 28: ...DigitAx User Guide Issue code dgxu4 4 8...
Страница 48: ...DigitAx User Guide Issue code dgxu4 5 20...
Страница 50: ...DigitAx User Guide Issue code dgxu4 6 2...
Страница 54: ...DigitAx User Guide Issue code dgxu4 8 2...
Страница 56: ...DigitAx User Guide Issue code dgxu4 9 2...
Страница 94: ...DigitAx User Guide Issue code dgxu4 13 6...