INSTALLATION
4–13
4.3.8 Reassembling the UPS Battery Cabinet
Perform the following steps:
1. Push the pull-out rack assembly into the UPS Battery Cabinet.
2. Replace the two bolts that secure the pull-out rack assembly to the sides of the unit.
They are located at the top left and top right side of the pull-out rack assembly. UPS
Battery Cabinets that have two pull-out rack assemblies (45-inches wide) have three
bolts securing them in place. One bolt secures the left pull-out rack assembly to the
left side of the unit in a similar manner to the single pull-out rack assembly. One
bolt secures the right pull-out rack assembly to the right side of the unit in a similar
manner to the single pull-out rack assembly. The third bolt secures the two pull-out
rack assemblies together at the center of the unit.
3. Replace the back top portion of the unit by forcing it on toward the front of the unit.
4. Replace the next portion of the top of the UPS Battery Cabinet by installing the two
screws located inside the ventilation openings at each side of the top of the unit.
5. Replace the top front corner piece on the UPS Battery Cabinet by installing the two
screws that hold it in place. These screws are located in a channel on the top of the
UPS Battery Cabinet.
6. Replace the red insulating panel(s) on the front of the battery rack(s).
7. Replace the back cover on the UPS Battery Cabinet.
8. Close the left door and install the screw at the top right portion of the left door, which
holds it in place.
9. Close the UPS Battery Cabinet right door.