3–4
HA3000 UPS RECEIVING AND HANDLING
3.3.4 Recommended Layout
The UPS Battery Cabinet should always be placed to the left of the UPS cabinet. The
UPS Auxiliary Cabinet is always bolted to the right side of the UPS cabinet. The UPS
CSA Cabinet is bolted to the right side of the UPS cabinet or to the right side of the UPS
Auxiliary Cabinet if a UPS Auxiliary Cabinet is installed. The UPS Distribution Cabinet
is bolted to the right side of the UPS Auxiliary Cabinet or to the right side of the UPS
CSA Cabinet if a UPS CSA Cabinet is installed. If a UPS Auxiliary Cabinet or a UPS
CSA Cabinet is not used, the UPS Distribution Cabinet is bolted to the right side of the
UPS cabinet. Figure 3–2 shows a typical HA3000 series UPS layout.
HA320-Ax
Remote Status Panel
HA32A
UPS
HA32C/D/E
UPS Auxiliary Cabinet
HA32J/K
UPS Distribution Cabinet
HA32B
UPS Battery Cabinet
MKV-A2078-91
Figure 3–2
HA3000 Series UPS Layout