2
SITE PREPARATION
2.1 GENERAL
This chapter contains site preparation information for the HA32A UPS cabinet, the
HA32B UPS Battery Cabinet, the HA32C/D/E UPS Auxiliary Cabinet, the HA33D/F UPS
CSA Cabinet, and the HA32J/K UPS Distribution Cabinet.
2.2 STORAGE
If the equipment is to be stored prior to installation, it should be stored in a cool, dry,
well-ventilated location that is protected against rain, splashing water, chemical agents,
and so forth. The equipment should be covered with a tarpaulin or plastic wrapper to
protect it against dirt, paint, or other foreign materials.
The UPS Battery Cabinet should be placed into service within 30 days from the date of
shipment, provided that the UPS Battery Cabinet is not stored in a location where it has
been exposed to temperature exceeding 25°C (77°F). Storage at higher temperatures will
reduce storage life, and may reduce battery life.
CAUTION
Never store batteries in a discharged condition. Always recharge batteries for
at least 24 hours before storage.
2–1