12
Reference & Installation Manual
4.6.5 Alarm Types
SECTION
[0400]: O
PTION
[2] & [6]
S
ECTIONS
[0101]
TO
[0196]: O
PTIONS
[5] & [6]
4.6.6 Intellizone*
SECTION
[0400]: O
PTION
[7]
S
ECTIONS
[0101]
TO
[0196]: O
PTION
[7]
(default =
032
) If an alarm condition occurs on a zone with option
[7]
enabled, the control panel triggers the Intellizone Delay. Fire Zones cannot
be set as Intellizones. An alarm will only be generated if the selected
conditions occur during the Intellizone Delay:
1.
An alarm occurs on another zone defined as Intellizone.
2.
The zone in alarm restores and reoccurs.
3.
The zone stays in alarm for the entire Intellizone Delay.
Key in the desired 3-digit delay value (010 to 255 seconds, default value is
32 seconds) into the section corresponding to the desired partition
Any value less than 10 seconds will be replaced by the default
value of 32 seconds.
* UL Note:
For UL Listed systems, the detection pattern of both zones must
be installed so that each zone has the capability of protecting the area alone.
4.6.7 Intellizone Options
Use these options to enable or disable different Intellizone related options.
Figure 14: Delayed 24Hr Fire Zone
4.6.8 Delay Before Alarm Transmission
SECTION
[0400]: O
PTION
[8]
S
ECTIONS
[0101]
TO
[0196]: O
PTION
[8]
(default =
000
) When an alarm condition occurs on a zone with option
[8]
enabled, the alarm will not be reported to the monitoring station until the
end of the Alarm Transmission Delay. Disarming the system cancels any
report originating from this zone. To program the Alarm Transmission Delay,
access section
[3055]
.
4.7 Input Speed
(001 to 255 X 30msec
,
default =
600ms
)
The Input Speed defines how quickly the control panel responds to an open
zone detected on any hardwired input terminal (does not apply to
addressable motion detectors and door contacts). Set the Input Speed (001
to 255 X 30ms, default =
600ms
):
Option Feature
Description
[5] [6]
OFF OFF
Steady Alarm
sends the report code and activates the bell
output
ON OFF
Pulsed Alarm
sends the report code and pulses the bell output
(see
OFF ON
Silent Alarm
sends the report code, but the bell output is not
activated. Partition must be disarmed.
ON
ON
Report Only
sends the report code. Disarming is not required.
Partition 1:
[3110]
Partition 3:
[3310]
Partition 5:
[3510]
Partition 7:
[3710]
Partition 2:
[3210]
Partition 4:
[3410]
Partition 6:
[3610]
Partition 8:
[3810]
Partition 1:
[3126]
Partition 3:
[3326]
Partition 5:
[3526]
Partition 7:
[3726]
Partition 2:
[3226]
Partition 4:
[3426]
Partition 6:
[3626]
Partition 8:
[3826]
Option Description
[1]
Intellizone Delay (default =
disabled
)
The zone stays in alarm for the entire Intellizone Delay.
[2]
Intellizone Double Knockout and Zone Crossing (default =
disabled
)
The zone in alarm restores and reoccurs or an alarm occurs on
another zone defined as Intellizone
[3]
Intellizone Zone Crossing (default =
disabled
)
An alarm occurs on another zone defined as Intellizone.
[5]
Police Code is Generated on Zone Crossing Only (default =
disabled
)
[0961]
Input 01
[0973]
Input 13 (ATZ of Input 01)
[0962]
Input 02
[0974]
Input 14 (ATZ of Input 02)
[0963]
Input 03
[0975]
Input 15 (ATZ of Input 03)
[0964]
Input 04
[0976]
Input 16 (ATZ of Input 04)
[0965]
Input 05
[0977]
Input 13 (ATZ of Input 01)
[0966]
Input 06
[0978]
Input 14 (ATZ of Input 02)
[0967]
Input 07
[0979]
Input 15 (ATZ of Input 03)
[0968]
Input 08
[0980]
Input 16 (ATZ of Input 04)
Latch alarm and transmit
report code as described
in
Delayed Fire Zone
Triggered
Bell/siren silenced. Delay report
transmission an additional 90s.
Activate bell/siren output & delay
report transmission for 30s.
Has the zone
closed within
30s?
Yes
Yes
Yes
Yes
No
No
No
No
Has a 2
nd
Delayed Fire
Zone opened
in 30s?
Any key on
keypad
pressed
within 30s?
Problem
corrected?
END
Alarm Disabled