EVO Control Panel

 47

3.5.11 Beep on Trouble

S

ECTION

 [005]: O

PTIONS

 [1] 

TO

 [4]

Option

 [1]

 OFF=Beep disabled: System Troubles and Clock Loss

Option

 [1]

 ON=Beep enabled: System Troubles and Clock Loss

Option

 [2]

 OFF=Beep disabled: Communicator Troubles

Option

 [2]

 ON=Beep enabled: Communicator Troubles

Option

 [3]

 OFF=Beep disabled: Module and Combus Troubles

Option

 [3]

 ON=Beep enabled: Module and Combus Troubles

Option

 [4] 

OFF=Beep disabled: all Zone Troubles

Option

 [4]

 ON=Beep enabled: all Zone Troubles

3.5.12 Keypad Tamper Enable

S

ECTION

 [006]: O

PTION

 [5]

Option

 [5]

 OFF=Keypad's tamper is disabled (default)

Option

 [5]

 ON=Keypad's tamper is enabled

3.5.13 Time Format

S

ECTION

 [005]: O

PTION

 [7]

Option 

[7]

 OFF=Time uses the International time format (default).

Option 

[7]

 ON=Time uses the US time format.

3.5.14 Combus Voltmeter

1.

From Normal Mode press and hold the 

[0]

 key.

2.

Enter the

 [

INSTALLER

 

CODE

]

 (by default 000000).

3.

Press 

[

ACC

].

The voltage may drop during the control panel battery test.

3.6 Access Control Options

3.6.1 Assigning Doors To Partitions

S

ECTION

 [002]: O

PTIONS

 [1] 

TO

 [8]

The Access Control door can be assigned to one or more partition(s) in the 
alarm system. This means that the actions performed with the Access 
Control Card will be directly linked to the partition(s) assigned to that door. 

Option

 [1]

 ON =Door assigned to Partition 1(default)

Option

 [2] 

ON =Door assigned to Partition 2

Option 

[3]

 ON=Door assigned to Partition 3

Option

 [4]

 ON =Door assigned to Partition 4

Option 

[5]

 ON=Door assigned to Partition 5

Option 

[6]

 ON=Door assigned to Partition 6

Option 

[7]

 ON=Door assigned to Partition 7

Option 

[8]

 ON=Door assigned to Partition 8

OFF  = Access Control Cards will not be able to arm and/or disarm 
partitions from the door's reader

3.6.2 Unlock on REX (Request For Exit)

S

ECTION

 [006]: O

PTION

 [8]

Option

 [8]

 OFF=Unlock on REX disabled (default)

Option

 [8]

 ON=Unlock on REX enabled

3.6.3 Door Unlocked Period

S

ECTION

 [008]

Enter any value between 001 and 255 to determine the seconds the door 
can remain unlocked. 

Default = 5 secs.

3.6.4 Door Unlocked Period Extension

S

ECTION

 [009]

The Door Unlocked Period Extension is the amount of time added to the 
Door Unlocked Period in section 

[008]

, which leaves the door unlocked 

longer. This will allow those with this feature enabled on their User Access 
Codes extra time to enter. Enter any value between 001 and 255 to 
determine the number of seconds to be added to the time programmed in 
section 

[008]

Default = 15 secs.

3.6.5 Relock Door

S

ECTION

 [006]: O

PTION

 [6]

Option

 [6]

 OFF=Locking device latches immediately (default)

Option 

[6]

 ON=Locking device latches when door closes

3.6.6 Door Unlocked Schedule

S

ECTION

 [017]

The Door Unlocked Schedule determines the hours, days, and holidays 
that the door will remain unlocked. Program the Start Time and End Time 
according to the 24-hour clock within the same day. Use 

Feature Select 

Programming

 to set the options representing the Days.

3.6.7 Card Activates Door Unlocked Schedule

S

ECTION

 [006]: O

PTION

 [1]

Option

 [1]

 OFF=The Schedule activates without Card

Option 

[1]

 ON=Card activates Door Unlocked Schedule (default)

3.6.8 Door Left Open Access Alarm

S

ECTION

 [006]: O

PTION

 [2]

Option 

[2] 

OFF=Door Left Open Alarm won’t be generated (default)

Option 

[2]

 ON=Door Left Open Alarm is enabled

3.6.9 Door Left Open Interval Before Access Alarm

S

ECTION

 [010]

Enter any value between 001 and 255 to determine the number of seconds 
the door may remain open before the Access Alarm is triggered. 

Default = 

60 secs.

3.6.10 Door Left Open Pre-Alarm

S

ECTION

 [004]: O

PTION

 [3]

Program the Pre-Alarm timer in section [011].

Option 

[3] 

OFF=The Pre-Alarm will not be generated

Option 

[3]

 ON=Pre-Alarm is enabled (default)

3.6.11 Door Left Open Pre-Alarm Timer

S

ECTION

 [011]

This timer will trigger the Door Left Open Pre-Alarm before the end of the 
Door Left Open Interval. Enter any value between 001 and 255 to 
determine the seconds before the expiry of the Door Left Open Interval that 
the reader will beep. 

Default = 15 seconds.

3.6.12 Door Left Open Alarm Feedback

S

ECTION

 [004]: O

PTIONS

 [5] 

AND

 [6]

Option

 [5]

 OFF=The Door Left Open Alarm is silent

Option 

[5]

 ON=The Door Left Open Alarm is audible (default)

If option 

[5]

 is enabled:

Option

 [6]

 OFF=Beep as long as the Door Left Open Alarm is

occurring (default)

Option

 [6]

 ON=Door Left Open Alarm follows Beep Timer (section [012])

Table 16: Door Unlocked Schedule

Option

Day

Option

Day

[1]

Sunday (S)

[5]

Thursday (T)

[2]

Monday (M)

[6]

Friday (F)

[3]

Tuesday (T)

[7]

Saturday (S)

[4]

Wednesday (W)

[8]

Holidays (H)

Table 17: Door Left Open Access Alarm

Section

[004] 

Option 

[3]

 Door Left Open Pre-alarm

Option 

[5]

 Door Left Open Alarm

Option 

[6]

 Door Left Open Alarm follows

[010]

Door Left Open Interval

[011]

Door Left Open Pre-alarm Timer

[012]

Beep Timer for Door Left Open Alarm

Содержание EVO192

Страница 1: ...High Security and Access System EVO48 V1 20 EVO192 V1 20 Installation Guide Includes Keypad Installation...

Страница 2: ......

Страница 3: ...rict Arming on Battery Failure 16 Restrict Arming on Bell or Auxiliary Failure 16 Restrict Arming on TLM Failure 16 Restrict Arming on Module Troubles 16 Timed Auto Arming 16 No Movement Auto Arming 1...

Страница 4: ...odes 34 Installer Code 34 Access Code Length 34 System Master Code 34 Programming Access Codes 34 User Options 34 Partition Assignment 35 Access Control 35 Access Control System Features 36 Common Acc...

Страница 5: ...tive triggering PGM1 can be used as a 2 wire smoke input 96 user codes 4 partitions 1024 events buffered Program remote controls using the master or installer codes Up to 96 remote controls with one M...

Страница 6: ...6 on page 30 2 5 1 Battery Test The control panel conducts a dynamic battery test under load every 60 seconds If the battery is disconnected if its capacity is too low or if the battery voltage drops...

Страница 7: ...ply and lead to complete system shutdown PLEASE NOTE When powering up the EVO control panel the panel will begin a module scan to verify if all the modules connected to the panel are operational The s...

Страница 8: ...Modules APR ZX8 _______ X 30mA __________ mA Magellan Wireless Expansion Modules MG RTX3 _______ X 35mA __________ mA 4 PGM Expansion Modules APR3 PGM4 _______ X 150mA __________ mA Printer Modules A...

Страница 9: ...terminal connections recognized by the Digiplex EVO system For UL listed installations use EOL resistor part 2011002000 Power required by devices connected to control panel s auxiliary output must no...

Страница 10: ...ences or across separate buildings use shielded cables Within the Same Building Strip the outer jacket at one end of the shielded cable to expose the shield and connect the shield to the control panel...

Страница 11: ...he control panel to transmit the Fire Loop Trouble report programmed in section 2906 To reset unlatch connect the smoke detector s negative to a PGM Then program the PGM with the Smoke Detector Power...

Страница 12: ...ntrol panel will save the data and go to the next section or press the ENTER key to save the data and go to the next section Press the CLEAR key go to the preceding step or to erase the current data e...

Страница 13: ...A Ademco express or Pager formats Key in desired 2 digit hex values from 00 to FF Ademco format Use section 4032 to program a set of default Ademco report codes from the Auto Report Code Programming o...

Страница 14: ...ntry Delay Timers To program an Entry Delay Timer key in the desired 3 digit delay value 001 to 255 seconds into the corresponding section These are the same timers used for Stay Delay zones 4 4 3 Fol...

Страница 15: ...steady or report only Fire alarms generate an intermittent signal see Figure 13 UL Warning For UL ULC installations a Fire Zone cannot be bypassed and its alarm type must be Pulsed audible Figure 13 B...

Страница 16: ...ion detectors and door contacts Set the Input Speed 001 to 255 X 30ms default 600ms Option Feature Description 5 6 OFF OFF Steady Alarm sends the report code and activates the bell output ON OFF Pulse...

Страница 17: ...rs enable option 7 in section 3033 For details on using EOL resistors refer to Addressable Zone Connections on page 5 and Double Zone Connections on page 6 4 9 Keypad Numbering SECTIONS 2801 TO 2832 K...

Страница 18: ...button Template To select a button template as the default template enter 00 to 15 representing button templates in sections 2900 to 2915 2941 Assign Button Template To assign a button template to a...

Страница 19: ...ility Key Event corresponding to the desired keyswitch see PGM Programming Table in the EVO Programming Guide Event Group 048 2 Enable option 4 in the section corresponding to the desired keyswitch 6...

Страница 20: ...considers all open zones as temporarily bypassed except 24hr zones The control panel transmits the Auto Arming report code programmed in section 3910 The control panel will transmit the Late to Close...

Страница 21: ...m the Magellan Wireless System MG RTX3 the control panel will cancel the Exit Delay and immediately arm the partition Enable option 8 in the desired section 7 18 3 Special Arming Exit Delay default 06...

Страница 22: ...n enabled the keypads will not display that zones have been bypassed while the system is armed Partition 1 3106 Partition 3 3306 Partition 5 3506 Partition 7 3706 Partition 2 3206 Partition 4 3406 Par...

Страница 23: ...e Options on page 12 to set it up so that a police code is only generated on Zone Crossing 8 5 Tamper Recognition Options SECTION 3034 OPTIONS 5 AND 6 When the control panel detects a tamper or wire f...

Страница 24: ...options 1 through 6 Report Only The keypad emits a single confirmation beep and transmits the report code Audible Alarm The control panel activates the BELL output until a user cancels the alarm or w...

Страница 25: ...ats on page 24 2 Auto Report Code Programming on page 26 Dialing sequences for Arm Disarm Report Codes Partition 1 3127 Partition 5 3527 Partition 2 3227 Partition 6 3627 Partition 3 3327 Partition 7...

Страница 26: ...use a common report code programmed in section 2199 The control panel can send the report code to the monitoring station identifying which access code was used to disarm the system It can be transmitt...

Страница 27: ...3943 Auxiliary Supply the aux power supply s current is greater than or equal to 1 1A 3944 Bell Output bell output is disconnected or the current is greater than or equal to 3A 3945 Clock Loss panel t...

Страница 28: ...Silent Knight fast and Sescoa standard pulse reporting formats see Table 6 9 7 2 Ademco Express The Ademco Express is a high speed reporting format that communicates 2 digit 00 to FF report codes The...

Страница 29: ...the test report code programmed into section 3902 every hour or after a period of time 9 15 Disarm Reporting Options default disabled When disabled the control panel sends the Disarming Report Codes...

Страница 30: ...n s Closing Delinquency Timer If the Closing Delinquency Timer elapses before the partition is armed again EVO will transmit a Closing Delinquency report code to the monitoring station Enter a value f...

Страница 31: ...e control panel switches from tone dialing to pulse dialing on the fifth attempt to report events to the monitoring station The control panel continues to use pulse dialing until it establishes commun...

Страница 32: ...8 3091 Telephone number 1 3095 Telephone number 5 3092 Telephone number 2 3096 Telephone number 6 3093 Telephone number 3 3097 Telephone number 7 3094 Telephone number 4 3098 Telephone number 8 3 Enab...

Страница 33: ...r the desired 3 digit number from the PGM Programming Table 12 5 PGM Timer When the PGM Deactivation Option is enabled the PGM Timer determines how many seconds or minutes the PGM remains activated En...

Страница 34: ...reconfigures 13 8 Transmit Zone Status on Serial Port SECTION 3035 OPTION 7 When enabled the control panel will transmit zone status information through the serial port Use this when there are device...

Страница 35: ...0 3200 3300 3400 3500 3600 3700 and 3800 to all the modules in the system that support these labels To transmit the labels in section 4004 enter the control panel s serial number From the Destination...

Страница 36: ...0 Partition 2 3200 Partition 4 3400 Partition 6 3600 Partition 8 3800 Table 7 Keys Press Feature Description STAY Insert Space Inserts a blank space in the cursor s position FORCE Delete Deletes the c...

Страница 37: ...92 108 124 172 188 204 220 236 252 045 061 077 093 109 125 173 189 205 221 237 253 046 062 078 094 110 126 174 190 206 222 238 254 047 063 079 095 111 127 175 191 207 223 239 255 016 032 048 064 080 0...

Страница 38: ...s code can arm or disarm the partitions All users can Regular arm their assigned partitions but only those with the Arm Only option disabled can disarm an assigned partition Enable or disable the opti...

Страница 39: ...access to an access control door by entering a code PIN and then pressing the ACC keypad button 14 7 4 Access Card Assignment SECTIONS 1002 TO 1999 ACCESS CARD SCREEN The Access Card is activated by a...

Страница 40: ...le is assigned to the door in sections 2201 to 2232 EVO supports up to 32 Doors 15 5 Access Levels SECTIONS 2601 TO 2615 Access Levels determine which Doors a user can access Each Access Level is a co...

Страница 41: ...l will no longer recognize the Schedules until the clock is reset Enable or disable the option as required 15 17 Burglar Alarm On Forced Door or Door Left Open SECTION 3038 OPTION 5 FORCED DOOR SECTIO...

Страница 42: ...then press the left action key Select To hang up highlight Cancel Communication and then press the left action key Select 16 7 Answering Machine Override Delay SECTION 3052 default 008 Program the Ans...

Страница 43: ...Upgrading EVO641 EVO641R Keypads To computer s 9 pin serial port DB 9 or USB To computer s USB port or 9 pin serial port DB 9 DB 9 Rx Tx PC LINK USB Product Link 307USB CONV4USB Battery or control pa...

Страница 44: ...d Cancel Alarm with PC Software 1 4A6 Cancel OR Disarm From Alarm Voice Disarm 1 4A7 Remote arm disarm OQ Remote Disarming Disarm with PC software 1 4A7 Remote arm disarm OQ Remote Disarming Disarm af...

Страница 45: ...tamper restore 3 145 Expansion module tamper restore TR Tamper Restoral Module ROM_RAM_error restore 3 3A4 Rom checksum bad restore YG Parameter Changed Module TLM restore 3 352 Telco 2 fault restore...

Страница 46: ...pliance chk 4 4E REMOTE ACCESS 410 137 Tamper 1A SYSTEM PERIPHERAL TROUBLES 330 340 411 Callback Request Made 83 138 Near Alarm 1B 330 System Peripheral 4F 412 Successful Download Access 84 139 Intrus...

Страница 47: ...5 Swinger Bypass BA 624 Event Log Overflow CF SOUNDER RELAY DISABLES 520 576 Access Zone Shunt BB 625 Time Date Reset D0 520 Sounder Relay Disabled A9 577 Access Point Bypass BC 626 Time Date Inaccura...

Страница 48: ...a confirmation beep wait 5 seconds and remove the memory key after the second confirmation beep 2 1 4 Copy the Keypad Contents to the Memory Key SECTION 520 1 Insert the memory key onto the keypad s c...

Страница 49: ...e the message to suit your installation needs 3 3 EVO641 Programming 3 3 1 Partition Assignment SECTION 001 OPTIONS 1 TO 8 To assign the keypad to a partition simply enable the option that corresponds...

Страница 50: ...d by a default Option 1 ON Access Code digits will be displayed 3 5 3 Display Exit Delay Timer SECTION 003 OPTION 2 Option 2 OFF Will not display Exit Delay timer default Option 2 ON LCD screen will d...

Страница 51: ...on their User Access Codes extra time to enter Enter any value between 001 and 255 to determine the number of seconds to be added to the time programmed in section 008 Default 15 secs 3 6 5 Relock Doo...

Страница 52: ...to more than one section For example you cannot assign value 002 to sections 003 and 004 The rejection beep will remind you that a selected display number is already assigned to another section 4 1 2...

Страница 53: ...Section 011 Option 5 Option 5 OFF Keypad s anti tamper is disabled default Option 5 ON Keypad s anti tamper is enabled 4 2 Programmable Output Options 4 2 1 PGM State SECTION 011 OPTION 1 The PGM is...

Страница 54: ...16 Timer 16 Auto Arming Options 17 Automatic Event Buffer Transmission 38 Automatic report code list 40 Auxiliary Power 2 Calculating power consumption 4 Power Limitations 4 Power Supply Connections 5...

Страница 55: ...Hr 11 Standard 24Hr 11 Follow Zone Switches to Entry Delay 2 17 Force Zones 11 Forced Door 36 Freeze Zones 11 Function Keys Installer 31 G Gas Zones 11 Ground 2 H Hardware Reset 30 Heat Zones 11 Hold...

Страница 56: ...e Ratio 27 Pulsed Audible Alarm 12 Q Quick Module Scanning 31 R Reader 36 Recent Close Delay 25 Record REX events 37 Recycle Alarm 19 Recycle Delay 19 Repeat Pager Report Code Transmission 25 Report C...

Страница 57: ...ransmitter Supervision Options 19 Z Zone Labels 32 Zone Restore Report Options 25 Zone Status Transmission to Serial Port 30 Zones Alarm Transmission Delay 12 Bypass 11 Connections 5 Definition 10 Del...

Страница 58: ...on This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However...

Страница 59: ...may be a group of buildings attached or unattached with different addresses but under the responsibility of someone having mutual interest The person of mutual interest is not the alarm installing com...

Страница 60: ...n a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all of the devices does not exceed 100 Industry Canada certification is only ap...

Страница 61: ...Notes...

Страница 62: ......

Страница 63: ......

Страница 64: ...any questions or comments please contact us For support please contact your local distributor or contact Paradox at 1 450 491 7444 Monday to Friday from 8 00 a m to 5 00 p m EST You may also e mail us...

Отзывы: