Reference & Installation Manual
4.1 Zone Programming
Two different methods can be used to program zones:
4.1.1 Using section [0400]
Allows you to program zones 001 through 192 as shown in the diagram on
page 9.
In any Zone Programming option, pressing [ACC] will save the data
and go to the next zone on the same option screen. Pressing
[TRBL] will save the data and go to the previous zone on the same
option screen.
4.1.2 Using zone serial and input numbers
If you are not using an EVO641 or an EVO641R keypad, you can only
program zones 1 to 96 through sections
[0001]
to
[0096].
4.2 Zone Numbering
S
ECTION
[0400]
S
ECTIONS
[0001]
TO
[0096]
• To assign an addressable PIR or door contact to the combus, program
the module’s serial number into the section corresponding to the zone.
• To assign a detection device connected to a module or control panel's
hardwired input terminal, program the module's or control panel's serial
number and the input number to the desired zone. See the “Digiplex
Modules Programming Guide” for details of its input numbers (input
numbers not required for keypad zones).
If PGM1 is defined as a smoke detector input (see section 12.6 on page 29), the
control panel will recognize it as input # 255.
4.2.1 Clearing a Zone’s Numbering
Using section [0400]
1.
Enter the zone number you wish to delete.
2.
Press
[0]
all the way through the serial/input, parameters and report
codes screen.
3.
Press
[
ENTER
]
to exit.
Using an LCD Keypad:
1.
Enter a section number between
[0001
] to
[0096]
.
2.
Press
[0]
and then
[
ENTER
]
to save and exit.
Using a Grafica Keypad:
1.
Enter a section number between
[0001]
to
[0096]
.
2.
Press
[0]
to clear the serial number.
3.
Highlight the input number and then press
[0]
to clear the data.
4.
Press Grafica’s center action key (
Save
) to save and exit.
4.3 Zone Doubling (ATZ)
S
ECTION
[3033]: O
PTION
[8]
(default =
disabled
) Fire Zones cannot be doubled.
4.4 Zone Definitions
4.4.1 Zone Disabled
SECTION
[0400]: F
IRST
DIGIT
= 0
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 0
Disables the corresponding zone. Zones are disabled by default.
4.4.2 Entry Delays 1 and 2
SECTION
[0400]: F
IRST
DIGIT
= 1
AND
2
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 1
AND
2
(default Entry Delay 1=
030
, Entry Delay 2 =
060
) A zone defined as Entry
Delay 1 follows the Entry Delay 1 Timer of its assigned partition. A zone
defined as Entry Delay 2 follows the Entry Delay 2 Timer of its assigned
partition. Each partition includes two Entry Delay Timers. To program an
Entry Delay Timer, key in the desired 3-digit delay value (001 to 255
seconds) into the corresponding section.
These are the same timers used for Stay Delay zones.
4.4.3 Follow Zones
SECTION
[0400]: F
IRST
DIGIT
= 3
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 3
The control panel waits until the end of the Entry Delay before generating
an alarm if an Entry Delay zone opens before the Follow zone.
4.4.4 Instant Zones
SECTION
[0400]: F
IRST
DIGIT
= 4
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 4
When an armed Instant zone opens, the control panel immediately
generates an alarm.
4.4.5 24Hr Buzzer Zones
SECTION
[0400]: F
IRST
DIGIT
= 5
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 5
Whenever a 24Hr Buzzer zone opens, the control panel activates the
keypad buzzer to indicate that the zone was breached. The control panel
will report the alarm, but will not enable the bell/siren output. Enter any valid
access code on the keypad to stop the buzzer.
The keypads must be assigned to the same partition as the 24Hr Buzzer zone or the
buzzer will not activate. UL Note: Not to be used for perimeter protection.
4.4.6 24Hr Burglary Zones
SECTION
[0400]: F
IRST
DIGIT
= 6
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 6
When a 24Hr Burglary zone opens, the control panel will immediately
generate a burglary alarm.
4.4.7 24Hr Hold-up Zones
SECTION
[0400]: F
IRST
DIGIT
= 7
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 7
When a 24Hr Hold-up zone opens, the control panel will immediately
generate an alarm.
The SIA FSK reporting format includes specific codes to identify the
alarm as a Hold-up, Gas, Heat, Water, or Freeze Alarm.
Zone
Number
Zone
Numbering
Zone
definitions
Zone Partition
Assignment
Zone Options
1
[0001]
[0101]
[0201]
[0301]
2
[0002]
[0102]
[0202]
[0302]
+1 per zone
+1 per zone
+1 per zone
+1 per zone
96
[0096]
[0196]
[0296]
[0396]
Input
Doubled Zone Input
Input 01
Input 09 (ATZ of Input 01)
Input 02
Input 10 (ATZ of Input 02)
Input 03
Input 11 (ATZ of Input 03)
Input 04
Input 12 (ATZ of Input 04)
Input 05
Input 13 (ATZ of Input 05)
Input 06
Input 14 (ATZ of Input 06)
Input 07
Input 15 (ATZ of Input 07)
Input 08
Input 16 (ATZ of Input 08)
Partition 1
Entry Delay 1 Timer:
[3111]
Entry Delay 2 Timer:
[3112]
Partition 2
Entry Delay 1 Timer:
[3211]
Entry Delay 2 Timer:
[3212]
Partition 3
Entry Delay 1 Timer:
[3311]
Entry Delay 2 Timer:
[3312]
Partition 4
Entry Delay 1 Timer:
[3411]
Entry Delay 2 Timer:
[3412]
Partition 5
Entry Delay 1 Timer:
[3511]
Entry Delay 2 Timer:
[3512]
Partition 6
Entry Delay 1 Timer:
[3611]
Entry Delay 2 Timer:
[3612]
Partition 7
Entry Delay 1 Timer:
[3711]
Entry Delay 2 Timer:
[3712]
Partition 8
Entry Delay 1 Timer:
[3811]
Entry Delay 2 Timer:
[3812]