DAEnetIP3
User Manual
-
27
-
When DI is in “Set output during rising edge” mode, the pulses are
started during rising edge of the DI level and during falling edge of the DI
level.
When DI is in “Set output during falling edge” mode the pulses are started
during rising edge of the DI level and stopped during falling edge of the
DI level.
7.5.13.
Pulses and analog input
Figure 23.
Pulses and analog input
In this mode (figure 23) when some analog input level crosses the given
threshold, the pulse generating is started or stopped. The user can not control
manually the outputs in this mode.
In “Low” mode pulses are started when the rising analog input level
crosses the LT+LH/2 limit and stopped when the falling analog input level
crosses the LT-LH/2 limit.
In “High” mode pulses are started when the rising analog input level
crosses the HT+HH/2 limit and stopped when falling analog input level
crosses the HT-HH/2 limit.
In “Acc” mode the pulses are started when the rising analog input level
crosses the HT+HH/2 and stopped when the rising analog input level
crosses the LT-LH/2.
In “Low/High” pulses are started when the rising (falling) analog input
level crosses the LT+LH/2 (HT-HH/2). The pulses are stopped when the
rising (falling) analog input level crosses the HT+HH/2 (LT-LH/2).