Figure 11.
Timer and digital input
7.5.18.
Timer and analog input
This mode combines the timer mode and analog inputs (figure 28). The user can
not control manually the outputs in this mode.
In “Low” mode the timer is started when the rising analog input level
crosses the LT+LH/2 limit.
In “High” mode the timer is started when the falling analog input level
crosses the HT-HH/2 limit.
In “Acc” mode the timer is started when the rising analog input level
crosses the HT+HH/2 limit.
In “Low/High” mode the timer is started when the rising analog input level
crosses the LT+LH/2 limit or the falling analog input level crosses the HT-
LH/2 limit.