Chapter 4 Parameters
VFD-EL-W
4-79
(
8 , O , 2
)
Start
bit
0
1
2
3
4
5
6
Stop
bit
8-data bits
12-bits character frame
Stop
bit
7
Odd
parity
Communication Protocol
1. Communication Data Frame
ASCII mode:
STX
Start character ‘:’ (3AH)
Address Hi
Communication address:
8-bit address consists of two ASCII codes.
Address Lo
Function Hi
Command code:
8-bit command consists of two ASCII codes.
Function Lo
DATA (n-1) to DATA 0
Contents of data:
Nx8-bit data consists of 2n ASCII codes.
n ≤ 20, maximum of 40 ASCII codes.
LRC CHK Hi
LRC checksum:
8-bit checksum consists of two ASCII codes.
LRC CHK Lo
END Hi
End characters:
END1 = CR (0DH), END0 = LF (0AH)
END Lo
RTU mode:
START
A silent interval of more than 10 ms
Address
Communication address: 8-bit address
Function
Command code: 8-bit command
DATA (n-1)
to
DATA 0
Contents of data:
n×8-bit data, n ≤ 40 (20 x 16-bit data).
CRC CHK Low
CRC checksum:
16-bit checksum consists of two 8-bit characters.
CRC CHK High
END
A silent interval of more than 10 ms
2. Address (Communication Address)
Valid communication addresses are between 0–254. A communication address of 0 means broadcast to all
AC motor drives (AMD). In this case, the AMD broadcast does not reply with any message to the master
device.
00H: broadcast to all AC motor drives
01H: AC motor drive with address 01
0FH: AC motor drive with address 15
10H: AC motor drive with address 16
:
FEH: AC motor drive with address 254
For example, send communication to AMD with address 16 decimal (10H):
ASCII mode: Address = ’1’,’0’ => ‘1’ = 31H, ‘0’ = 30H
RTU mode: Address = 10H
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...