Chapter 4 Parameters
VFD-EL-W
4-104
Parameter
Function
Settings
Default
End
user’s
master
End
user’s
slave
Note
01.00
Maximum
Output
Frequency
(Fmax)
50.00–400.0 Hz
60.00 60.00 60.00
Follows the specifications of
pumps
01.01
Motor Rated
Frequency
(Fbase)
0.10–400.0 Hz
60.00 60.00 60.00
01.02
Motor Rated
Voltage
(Vbase)
230V series: 0.1–255.0 V
220.0 220.0 220.0
460V series: 0.1–510.0 V
440.0
01.09 Accel. Time 1
0.1–600.0 / 0.01–600.00 sec. 10.0
0.5
0.5 Adjusts according to
customer’s applications
01.10 Decel. Time 1 0.1–600.0 / 0.01–600.00 sec. 10.0
5.0
5.0
01.12 Decel. Time 2 0.1–600.0 / 0.01–600.00 sec. 10.0
3.0
3.0
The time the AC motor drive
decelerates to stop when the
pressure reaches the setting
value.
Parameter
Function
Settings
Default
End
user’s
master
End
user’s
slave
Note
02.00
First Master
Frequency
Command
Source
0: Digital keypad UP/DOWN
keys or Multi-function
Inputs UP/DOWN.
1: 0–10 V from AVI
2: 4–20 mA from ACI
3: RS-485 (RJ45)
communication
4: Digital keypad
potentiometer
0
2
2
Adjusts according to
customer’s applications
02.01
First Operation
Command
Source
0: Digital keypad
0
0
0
Adjusts according to
customer’s applications
1: External terminals.
Keypad STOP/RESET
enabled.
2: External terminals.
Keypad STOP/RESET
disabled.
3: RS-485 communication.
Keypad STOP/RESET
enabled.
4: RS-485 communication.
Keypad STOP/RESET
disabled.
Parameter
Function
Settings
Default
End
user’s
master
End
user’s
slave
Note
10.00
PID Set Point
Selection
0: Disable
0
1
1
Adjusts according to
customer’s applications
1: Digital keypad UP/DOWN
keys
2: Reserved
3: Reserved
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...