Chapter 4 Parameters
VFD-EL-W
4-43
02.12
Communication Frequency Command
Unit: 0.01
Settings
0.00–400.00 Hz
Default: 60.00
Sets the frequency command or reads the communication frequency command.
02.13
Saving Keypad or Communication Frequency Command Selection
Default: 0
Settings
0: Save Keypad & Communication Frequency
1: Save Keypad Frequency Only
2: Save Communication Frequency Only
Saves the keypad or RS-485 frequency command.
02.14
Initial Frequency Selection (for Keypad & RS-485)
Default: 0
Settings
0
Current Frequency Command
1
Zero Frequency Command
2
Refer to Pr.02.15 to set up
02.15
Initial Frequency Setting (for Keypad & RS-485)
Unit: 0.01
Settings
0.00–400.00 Hz
Default: 60.00
Determinates the frequency at stop.
Pr.02.14=0: The initial frequency is the current frequency.
Pr.02.14=1: The initial frequency is 0.
Pr.02.14=2: The initial frequency is the Pr.02.15 setting.
02.16
Display the Master Frequency Command Source
Settings
Read Only
Default: Read Only
You can read the master frequency command source from this parameter.
Display Value
Bit
Function
1
bit0=1
The Master Frequency Command Source is the First Master Frequency
Source (Pr.02.00).
2
bit1=1
The Master Frequency Command Source is the Second Master Frequency
Source (Pr.02.09).
4
bit2=1 The Master Frequency Command Source is the Multi-function input.
02.17
Display the Operation Command Source
Settings
Read Only
Default: Read Only
You can read the operation command source from this parameter.
Display Value
Bit
Function
1
bit0=1 Operation Command Source is the Digital Keypad
2
bit1=1 Operation Command Source is the RS-485 communication
4
bit2=1 Operation Command Source is the External Terminal (MI1)
8
bit3=1 Operation Command Source is the Multi-function Input
02.18
User-defined Value 2 Setting
Settings
0–Pr.00.13
Default: 0
Reads and writes the user-defined value settings. Changes the operation frequency when Pr.00.13 is not set
to 0 and frequency source is from communication.
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...