Chapter 4 Parameters
VFD-EL-W
4-42
When you set Pr.02.05 to 1 or 3, it does not guarantee that the motor will never run under this condition. It is
possible the motor may be set in motion by a malfunctioning switch.
02.06
Loss of ACI Signal (4–20 mA)
Default: 0
Settings
0: Decelerate to 0 Hz
1: Coast to stop and display “AErr”
2:
3:
Continue the operation according to the last frequency command
Continue the operation according to the setting at Pr.02.11.
Determines the action when ACI signal is lost.
1: Display the warning message “AErr” on the keypad when the ACI signal is lost and execute the Pr.02.06
setting. When the ACI signal is recovered, the warning message atomically stops blinking. You can also press
“STOP/RESET” to clear the warning message.
02.07
Up/Down Mode
Default: 0
Settings
0: Digital keypad up/down keys mode
1: Based on Accel./ Decel. Time
2: Constant speed (according to Pr.02.08)
3: Pulse input unit (according to Pr.02.08)
02.08
Accel. / Decel. Rate of Change of UP / DOWN Operation with Constant
Speed
Unit: 0.01
Settings
0.01–10.00 Hz/2ms
Default: 0.01
Determine the increase / decrease of the master frequency when operated through the multi-function inputs
and you set Pr.04.06–Pr.04.08 10 (Up command) or 11 (Down command).
Pr.02.07=0: Use the external terminal’s UP/DOWN keys to increase or decrease the frequency. This is valid
only when the AC motor drive is running.
Pr.02.07=1: Increase and decrease the frequency by the acceleration and deceleration settings. This is valid
only when the AC motor drive is running.
Pr.02.07=2: Increase and decrease the frequency by Pr.02.08 settings.
Pr.02.07=3: Increase and decrease the frequency according to Pr.02.08 (unit: pulse input). Every ON after
OFF is regarded as an input pulse.
02.11
Keypad Frequency Command
Unit: 0.01
Settings
0.00–400.00 Hz
Default: 60.00
Sets the frequency command or reads the keypad frequency command.
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...