Chapter 4 Parameters
VFD-EL-W
4-40
Take VFD007EL21W(-1) as an example, assume that the ambient temperature is 40°C, the drive output
current must be controlled within 100% of the rated current. If the ambient temperature is 50°C, the drive
output current should not exceed 80% of the rated current. For other models in an ambient temperature of
50°C, the drive output current must be controlled within 100% of the rated current; for other models in an
ambient temperature of 60°C, the drive output current must be controlled within 80% of the rated current.
Take VFD007EL21W(-1) as an example, assume that the ambient temperature is 40°C, and default carrier
frequency is 8 kHz, then the drive output current reaches 100% of the rated current; if the carrier frequency is
12 kHz, the drive output current must be controlled within 80% of the rated current. If the ambient temperature
is 25°C, the installation method is single drive installation, and the carrier frequency is 12 kHz, then the drive
reaches 100% of the rated current.
NOTE
Other models: VFD002EL21W(-1), VFD004EL21W(-1), VFD015EL21W(-1), VFD022EL21W(-1),
VFD004EL43W(-1), VFD007EL43W(-1), VFD015EL43W(-1), VFD022EL43W(-1), VFD040EL43W(-1)
02.04
Motor Direction Control
Default: 0
Settings
0:
Forward / Reverse operation enabled
1:
Reverse operation disabled
2:
Forward operation disabled
Disables one direction of rotation for the AC motor drive.
02.05
Power-On Command and Run Command Source Modifies the Drive Operating Control
Default: 1
Settings
0: Start running when power is on.
1: Do not run when power is on.
2: When the source of the command changes, the drive’s operation remains the
same.
3: When the source of the command changes, the drive’s operation follows the new
command.
4: The motor drive can start to run at power on or after reset.
When the source of the command is a two-wire external terminal, the operating
Ambient temperature (
°
C)
Other models
R
at
ed
c
ur
re
nt
(
%
)
Carrier Frequency (kHz)
Other models 40°C
All models 25°C
R
at
ed
c
ur
re
nt
(
%
)
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...