Chapter 4 Parameters
VFD-EL-W
4-94
10.43
Pump’s Error Treatment
Settings
Bit0–Bit2
Default: 1
This parameter is only valid for master pump settings.
Bit0: Determines whether the erroneous pump switches to an alternative pump when an error occurs in the
running pump.
0: All pumps stop.
1: Switch to an alternative pump
Example:
When Bit0=0, and if an error occurs in the running pump, all pumps stop.
When Bit0=1, and if an error occurs in the running pump, switch the erroneous pump to an alternative pump.
Bit1: Determines the erroneous pump to be in a standby or stop status after reset.
0: Set the erroneous pump to be in a standby status after reset (the pump receives the RUN command).
1: Set the erroneous pump to be in a stop status after reset (the pump does not receive the RUN command).
Example:
When Bit1=0, and after resetting the erroneous pump, you can control its running through the controller.
When Bit1=1, and after resetting the erroneous pump, you cannot control its running through the controller
until the master pump gives the STOP command.
Bit2: Determines whether the master pump receives the RUN command or not when an error occurs in the
running pump.
0: When an error occurs in the running pump, the master pump does not receive the RUN command.
1: When an error occurs in the running pump, the master pump can choose to run with an alternative pump,
instead of the erroneous pump.
Example:
When Bit2=0, the master pump does not receive the RUN command when an error occurs in drive #2.
When Bit2=1, the master pump receives the RUN command and choose to run with an alternative pump
when an error occurs in drive #2.
This parameter setting is only valid for AUTO mode.
10.44
Selection of Pump’s Start-up Sequence
Settings
0–1
0: By pump ID#
1: By running time
Default: 0
0: By pump ID#, (1
2
3
4
1)
1: By the shortest running time
10.45
Running Time of Multi-pump Under Alternative Operation
Settings
0.0–360.0 sec.
Default: 60.0
This parameter is only valid for master pump settings.
Sets the time for switching the master pump and the slave pump.
10.46
Reserved
10.47
Reserved
10. 48
Reserved
10.49
Specify the Setting for Pr.10.12 [PID Deviation Level]
Settings
0–1
0: Use the existing setting (default), and check for any error per the
feedback deviation.
1: Set the low water pressure percentage (%), and check for any error
per the physical quantity feedback.
Default: 0
When the pressure sensor is set to 10 kg, Pr.10.49=0 and Pr.10.12=10.0% (that is, deviation=1 kg), and if
the set point=3 kg and feedback < 2 kg, then the AC motor drive follows the setting for Pr.10.20.
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...