Chapter 4 Parameters
VFD-EL-W
4-71
Settings
0.1–5.0 sec.
Default: 0.5
When the AC motor drive detects a momentary power loss, it blocks its output and then waits for a period of
time specified by this parameter before resuming operation. Set this parameter at a value that ensures that
any residual regeneration voltage from the motor on the output has disappeared before the drive is activated
again.
This parameter also determines the waiting time before resuming operation after an External Base Block and
Number of Auto-restarts after Fault (Pr.08.15).
08.08
Current Limit for Speed Search
Unit: 1
Settings
30–200%
Default: 150
Limits the drive output current during a speed search.
When executing a speed search, the V/F curve is defined by the settings in Parameter Group 01.
08.09
Skip Frequency 1 Upper Limit
Unit: 0.01
08.10
Skip Frequency 1 Lower Limit
Unit: 0.01
08.11
Skip Frequency 2 Upper Limit
Unit: 0.01
08.12
Skip Frequency 2 Lower Limit
Unit: 0.01
08.13
Skip Frequency 3 Upper Limit
Unit: 0.01
08.14
Skip Frequency 3 Lower Limit
Unit: 0.01
Settings
0.00–400.00 Hz
Default: 0.00
These parameters cause the AC motor drive not to remain in these frequency ranges with continuous
frequency output. Set these six parameters as follows Pr.08.09
Pr.08.10
Pr.08.11
Pr.08.12
Pr.08.13
Pr.08.14.
0
08.09
08.10
08.11
08.12
08.13
08.14
setting frequency
in
te
rn
a
l f
re
q
u
e
n
cy
c
o
m
m
a
n
d
08.15
Number of Auto-restarts After Fault
Unit: 1
Settings
0–10
Default: 0
08.16
Auto-reset Time for Restart after Fault
Unit: 0.1
Settings
0.1–6000 sec.
Default: 60.0
After an over-current OC or over-voltage OV fault occurs, the AC motor drive can automatically reset/restart
up to ten times.
Setting this parameter to 0 disables automatic reset/restart operation after any fault.
When enabled, the AC motor drive restarts with speed search, which starts at the last frequency before the
fault.
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...