Chapter 6 Fault Code Information and Maintenance
VFD-EL-W
6-2
6.1 Fault Code Information
The following messages display when the operation command source is set as digital keypad.
Fault Name
Fault Descriptions
Corrective Actions
Over-current
Abnormal increase in current.
1. Check if the motor power corresponds with the AC
motor drive output power.
2. Check the wiring connections to U/T1, V/T2, and
W/T3 for possible short circuits.
3. Check the wiring connections between the AC motor
drive and motor for possible short circuits, and for
short to ground.
4. Check for loose contacts between the AC motor drive
and the motor.
5. Increase the Acceleration Time.
6. Check for possible excessive loading on the motor.
Over-voltage
The DC bus voltage exceeds its
maximum allowable value.
1. Check if the input voltage is in the rated AC motor
drive input voltage range.
2. Check for possible voltage transients.
3. DC bus over-voltage may also be caused by motor
regeneration. Either increase the Deceleration Time
or add an optional brake resistor (and brake unit).
Overheating
Heat sink temperature is too high.
1. Ensure that the ambient temperature is in the
specified temperature range.
2. Make sure that the ventilation holes are not
obstructed.
3. Provide enough spacing for adequate ventilation. (see
Chapter 1)
Low voltage
The AC motor drive detects that
the DC bus voltage has fallen
below its minimum value.
1. Check whether the input voltage is in the AC motor
drive rated input voltage range.
2. Check for abnormal load on the motor.
3. Check for correct input power wiring to R-S-T (for
three-phase models) without phase loss.
Overload
The AC motor drive detects
excessive drive output current.
NOTE: The AC motor drive can
withstand up to 150% of the rated
current for a maximum of 60
seconds.
1. Check whether the motor is overloaded.
2. Reduce the torque compensation setting (Pr.07.02).
3. Use the next higher power AC motor drive model.
Overload 1
Internal electronic overload trip
1. Check for possible motor overload.
2. Check the electronic thermal overload setting.
3. Replace the drive with a larger capacity model.
4. Reduce the current level so that the drive output
current does not exceed the value in the Motor Rated
Current (Pr.07.00).
Overload 2
Motor overload.
1. Reduce the motor load.
2. Adjust the over-torque detection settings to
appropriate values (Pr.06.03–Pr.06.05).
CC (current clamp)
Return the unit to the factory.
OV hardware fault
Return the unit to the factory.
OC hardware fault
Содержание VFD-EL-W Series
Страница 7: ...v This page intentionally left blank ...
Страница 21: ...Chapter 1 Introduction VFD EL W 1 14 This page intentionally left blank ...
Страница 34: ...Chapter 2 Installation and Wiring VFD EL W 2 13 This page intentionally left blank ...
Страница 42: ...Chapter 3 Keypad and Start up VFD EL W 3 8 This page intentionally left blank ...
Страница 150: ...Chapter 4 Parameters VFD EL W 4 108 This page intentionally left blank ...
Страница 152: ...Chapter 5 Troubleshooting VFD EL W 5 2 5 1 Over Current oc ...
Страница 153: ...Chapter 5 Troubleshooting VFD EL W 5 3 5 2 Over Voltage ov ...
Страница 154: ...Chapter 5 Troubleshooting VFD EL W 5 4 5 3 Low Voltage Lv ...
Страница 155: ...Chapter 5 Troubleshooting VFD EL W 5 5 5 4 Overheat oH1 ...
Страница 156: ...Chapter 5 Troubleshooting VFD EL W 5 6 5 5 Overload oL ...
Страница 157: ...Chapter 5 Troubleshooting VFD EL W 5 7 5 6 Keypad Display is Abnormal 5 7 Phase Loss PHL ...
Страница 158: ...Chapter 5 Troubleshooting VFD EL W 5 8 5 8 Motor Does Not Run ...
Страница 159: ...Chapter 5 Troubleshooting VFD EL W 5 9 5 9 Motor Speed Cannot be Changed ...
Страница 160: ...Chapter 5 Troubleshooting VFD EL W 5 10 5 10 Motor Stalls During Acceleration 5 11 The Motor Does Not Run as Expected ...
Страница 163: ...Chapter 5 Troubleshooting VFD EL W 5 13 This page intentionally left blank ...
Страница 173: ...Chapter 6 Fault Code Information and Maintenance VFD EL W 6 10 This page intentionally left blank ...
Страница 179: ...Appendix A Specifications VFD EL W A 6 This page intentionally left blank ...
Страница 186: ...Appendix B Accessories VFD EL W B 7 B 3 1 3 Operation Flow Chart Write parameters failure Write parameters success ...
Страница 190: ...Appendix B Accessories VFD EL W B 11 3 Replace the top cover to complete the cooling fan installation ...
Страница 197: ...Appendix C How to Select the Right AC Motor Drive VFD EL W C 7 This page intentionally left blank ...