32
Pr.31
Pr.30
DC brake starting frequency
Pr.28
DC braking current %
Pr.29
Minimum output
frequency
Pr.08
Pr.32 Pr.33 Pr.34 Pr.35
Momentary Power Loss Protection
Parameter #
32
Parameter Name
Momentary power failure operation mode
Factory Setting
d0000
Settings
d0000 Operation stops after momentary power loss
d0001 Operation continues after momentary power loss.
Speed search starts with the frequency reference value
d0002 Operation continues after momentary power loss.
Speed search starts with the Minimum output frequency, Pr.08
Note
Multi-function Indication and Photocoupler outputs that are
programmed for “fault indication” will not be energized during
restart after a momentary power failure. (refer to Pr. 45 and 57)
This parameter determines the AC drive mode of operation after recovery from a
momentary power failure.
Parameter #
33
Parameter Name
Maximum allowable power loss time
Factory Setting
d002.0 Sec
Units
0.1 Sec
Parameter value
d000.3 - d005.0 Sec
If during a power failure the power loss is less than the time defined by Pr.33, then
the AC drive will resume operation (set by Pr.32). If the maximum allowable power
loss time is exceeded, the AC drive output power will remain off and must be reset
to resume operation (the fault indication will be set).
Parameter #
34
Parameter Name
Minimum base block time
Factory Setting
d000.5 Sec
Units
0.1 Sec
Parameter value
d000.3 - d005.0 Sec
When a momentary power loss is detected and the power failure is less than the
time set by Pr.33, the AC drive output will resume operation after the specified
period of time determined by Pr.34. This parameter should be set to a value where
the residual output voltage is nearly zero.
Содержание VFD-A
Страница 1: ......
Страница 2: ...5011200503 200305 22 AE02...
Страница 3: ......
Страница 65: ...61 APPENDIX A Standard Specifications...
Страница 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Страница 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Страница 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...