63
Voltage classification
460V
Model name VFD-
007 015 022 037 055 075 110 150 185 220
3 Phase motor rating (KW)
0.75
1.5
2.2
3.7
5.5
7.5
11.0
15.0
18.5
22.0
3 Phase motor rating (HP)
1.0
2.0
3.0
5.0
7.5
10.0
15.0
20.0
25.0
30.0
Inverter output (KVA)
2.3
3.2
4.2
6.3
9.9
13.7
18.3
24.4
28.9
34.3
Output current (A)
3
4.2
5.5
8.2
13
18
24
32
38
45
Output voltage (V)
Adjustable from 0 to input voltage
Output Rating
Output frequency (Hz)
Programmable from 0 to 400 Hz
Rated AC input power supply
380 / 400 / 415 / 480 VAC, three phase, 50 / 60Hz
Input Current (A)
4.2
43A
5.8
43B
6.0
7.2 8.5 14.0
20.6
28 30 39 49
Operational range (V)
340
∼
500 VAC, 47
∼
63 Hz
Input Rating
Power factor (Displacement)
0.8 (Lagging)
Control system
Sinusoidal PWM control
Frequency control range
0.1
∼
400.0 Hz
Frequency setting resolution
0.1 Hz
Output frequency resolution
0.1 Hz
Overload current rating
150% of rated current for 1 minute
Acceleration / deceleration time
0.1
∼
600.0 Sec
Torque characteristics
Starting torque 150% or more (at 5 Hz)
Regenerative braking
Incorporate regenerative braking circuit
V / F pattern
Any V / F pattern setting
Control Characteristics
Stall prevention level
Setting to percentage of rated current
Digital operation
﹑
Setting by
or
JOG
Frequency
setting
External signal
Variable resistor of 5K/ 0.5W, 0 to 10 VDC, 4
∼
20mA, RS-485 serial port,
Multi-function 1
∼
3(JOG, Multi-step speed, Up / Down)
Digital operation Setting by RUN, STOP, FWD / REV
Operation Setting
Signal
External signal
FWD, REV, EF can be combined for 2 or 3-wire operation, RS-485 serial interface.
Multi-function input signal
Multi-step selection 1
∼
7, Jogging, Accel. / Decel. Prohibit, First / Second
Accel. / Decel. Switching command, External BB (NC, NO selection), etc.
Multi-function output signal
During running, Up to frequency setting, Up to desired frequency setting Count out
detection, Non zero-speed, Over-torque detection, etc.
Operating Characteristics
Analog / Digital Output
Analog frequency / current signal output, digital frequency signal output
Other functions
Automatic Voltage Regulation (AVR), S-Curve, over voltage, over-current stall prevention,
abnormal records checking, Carrier-frequency adjustable, DC braking, DB starting
frequency setting, Momentary power failure restart, Frequency limit, etc.
Protective function
Over-current, over voltage, under voltage, electronic thermal, overheat ground fault,
overload limit, over voltage supply, etc., but no short-circuit protection of output terminals.
Cooling Method
Forced air-cooling
Installation site
Altitude 1,000m or lower, keep from corrosive gasses, liquid and dust
Pollution Degree
2
Ambient temperature
-10
°
C
∼
40
°
C (-10
°
C
∼
50
°
C without blind plate) at rated voltage and rated current.
Storage temperature
-20
°
C
∼
60
°
C
Ambient Humidity
Below 90% RH (non-condensing)
Environments
Vibration
1.0G less than 20Hz, 0.6G at 20
∼
50Hz
Options
EG2010A extension cable, LC-A05E, LC-A10E digital keypad, RC-01 remote control unit,
MVR / MHR Braking resistor
Note 1: The frequency can be reached to 1500Hz by VFD-H Series AC Motor Drives.
Note 2: 11Kw
∼
22Kw models, exclude inherent braking transistor, external braking is optional.
Содержание VFD-A
Страница 1: ......
Страница 2: ...5011200503 200305 22 AE02...
Страница 3: ......
Страница 65: ...61 APPENDIX A Standard Specifications...
Страница 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Страница 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Страница 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...