34
Pr.37
Pr.36
Input frequency
Output frequency
External Control Terminal
Pr.38
External Control Terminal Configuration
Parameter #
38
Parameter Name
2-wire / 3-wire operation control selection
Factory Setting
d0000
Settings
d0000 FWD / STOP, REV / STOP
d0001 FWD / REV, RUN / STOP
d0002 3-WIRE operation control mode
This parameter determines the control functions and operating modes available
through the external control terminals. The following configurations are available:
Pr.38
Control terminal wiring diagram
d0000
Two wire
FWD / STOP
REV / STOP
REV
FWD
REV/STOP
FWD/STOP
VFD-A
DCM
"Open" : Stop; "Close" : FWD Run
"Open" : Stop; "Close" : REV Run
d0001
Two wire
REV / FWD
RUN / STOP
REV/FWD
RUN/STOP
REV
FWD
DCM
"Open" : Stop; "Close" : Run
"Open" : FWD; "Close" : REV
VFD-A
d0002
Three wire
REV/FWD
RUN
STOP
EF
FWD
DCM
(Run command, Runs when "Close)
(Stop command, stops when "Open")
REV ( REV/FWD Run select
"Open" : FWD Run
"Close" : REV Run)
VFD-A
Содержание VFD-A
Страница 1: ......
Страница 2: ...5011200503 200305 22 AE02...
Страница 3: ......
Страница 65: ...61 APPENDIX A Standard Specifications...
Страница 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Страница 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Страница 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...