25
Accel / Decel Time Setting
Pr.10 Pr.11 Pr.12 Pr.13
Accel / Decel Time Setting
Parameter #
10
Parameter Name
Acceleration Time 1
Factory Setting
d010.0 Sec
Units
0.1 Sec
Parameter value
d000.1 - d600.0 Sec
This parameter can be programmed while the drive is running.
This parameter is used to determine the time required for the AC drive to ramp from
0 Hz to its Maximum operating frequency (Pr.03). The rate is linear unless S Curve
is “Enabled.”
Parameter #
11
Parameter Name
Deceleration Time 1
Factory Setting
d010.0 Sec
Units
0.1 Sec
Parameter value
d000.1 - d600.0 Sec
This parameter can be programmed while the drive is running.
This parameter is used to determine the time required for the AC drive to decelerate
from the Maximum operating frequency (Pr.03) down to 0 Hz. The rate is linear
unless S Curve is
“
Enabled.
”
Time
Speed
Accel
Time
Decel
Time
Pr.10
Pr.11
Pr.12
Pr.13
or
or
Command frequency