Start-up
This chapter describes the steps needed to start the AC drive and typical adjustment
and verification procedures to ensure a simple and efficient start-up. The following
start-up procedures describe the most common parameter settings and system
configurations.
Initial Operation - Motor Disconnected
Verify that the AC power line, at the disconnect device, is within the rated power
of the AC drive.
Disconnect and lockout all incoming power to the drive.
Connect the AC drive to the power line.
Reconnect the incoming power to the drive.
Proceed as follows to select a mode of operation.
1. Operating frequency determined by the digital keypad,
Digital keypad enabled to control AC drive operation.
(Pr.00 = d0000, Pr.01 = d0000) (Factory default setting)
IM
2. Operating frequency determined by the digital keypad,
Control terminals enabled to control AC drive operation; ”Stop” key on digital
keypad is enabled.
Two wire “REV/STOP” and “FWD/STOP” remote control enabled.
(Pr.00 = d0000, Pr.01 = d0001, Pr.38 = d0000)
REV/STOP
FWD/STOP
IM
FWD
REV
DCM