29
Pr.25
Over-voltage Stall Prevention
Parameter #
25
Parameter Name
Over-voltage stall prevention during deceleration
Factory Setting
d0001
Settings
d0000 Disable over-voltage stall prevention
d0001 Enable
over-voltage stall prevention
During deceleration, the motor DC bus voltage may exceed its maximum allowable
value due to motor regeneration. When Pr.25 is enabled and an over-voltage is
detected, the AC drive will cease to decelerate and will then maintain a constant
output frequency. The drive will only resume deceleration when the DC bus voltage
drops below the preset value.
Time
DC bus
voltage
Over voltage
detection
level
Output
frequency
Time
Over voltage stall prevention
Pr.26 Pr.27
Over-current Stall Prevention
Parameter #
26
Parameter Name
Over-current stall prevention during acceleration
Factory Setting
d0170 %
Units
1%
Parameter value
d0050 - d0200 %
During periods of rapid acceleration or excessive load on the motor, the AC drive
output current may increase abruptly and exceed the value specified by Pr.26.
When over-current occurs, the AC drive will cease to accelerate and will maintain a
constant output frequency until the current falls below the preset value. (The drive
will only resume acceleration when the current drops below the preset value.)
Содержание VFD-A
Страница 1: ......
Страница 2: ...5011200503 200305 22 AE02...
Страница 3: ......
Страница 65: ...61 APPENDIX A Standard Specifications...
Страница 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Страница 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Страница 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...