39
Pr.47
Desired Frequency Attained Setting
Parameter #
47
Parameter Name
Desired frequency attained setting
Factory Setting
d000.0 Hz
Units
0.1 Hz
Parameter value
d000.0 - d400.0 Hz
Used to select a specified frequency, set in increments of 0.1 Hz. ( See Pr.45, 46 )
Pr.48 Pr.49
Analog Input Setting for Output Frequency Range
Parameter #
48
Parameter Name
Maximum output frequency voltage setting
Factory Setting
d010.0 V
Units
0.1 V
Parameter value
d000.0 - d010.0 V
This parameter can be programmed while the drive is running.
Sets the
input signal voltage level (0 – 10V) that corresponds to the
maximum
output frequency
(Pr.03). Used in conjunction with Pr.49, this parameter may be
used to set the analog input for frequency command curve setting. (See graph on
next page)
Parameter #
49
Parameter Name
Minimum output frequency voltage setting
Factory Setting
d000.3 V
Units
0.1 V
Parameter value
d000.0 - d010.0 V
This parameter can be programmed while the drive is running.
Sets the input signal voltage level (0 – 10V) that corresponds to the
minimum
output frequency
(Pr.08). (See graph on next page)
Note: The absolute value of the difference between the settings of Pr.48 and Pr.49
should be greater than or equal to 3.
Содержание VFD-A
Страница 1: ......
Страница 2: ...5011200503 200305 22 AE02...
Страница 3: ......
Страница 65: ...61 APPENDIX A Standard Specifications...
Страница 77: ...73 Remote Controller RC01 Adapter Unit mm inches Standard Extension Cable Unit mm...
Страница 79: ...75 Braking Resistors Braking Units Braking Resistors Braking Units...
Страница 80: ...76 Braking resistors model no BR1K0W050 BR1K2W008 BR1K2W6P8 BR1K5W005 BR1K5W040...