7 - 1 8
Ultron DPS Series
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD PROTECTED
ON BATTERY
TO BROWSE EVENT
(004)
PRESS
5
After you complete the battery mode start-up procedures, each unit’s LEDs illuminate
as follows.
Fault
7.2.3 Bypass Mode Start-up Procedures (Parallel)
1
Switch on each UPS's Bypass Switch (Q2). After initialization, all fans start running,
each unit's Bypass AC Source LED
and Bypass Power Supply LED
illuminate,
and the following screen appears on each UPS's screen.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
TO BROWSE EVENT
(004)
PRESS
2
Turn on each unit’s UPS Output Switch (Q4). Each unit’s Output Switch LED
illuminates and each unit’s LCD shows the following screen. At this moment, the
bypass supplies power to the output.